For example, the ID selectors in figure 12.8 show 
address 2C.
Make sure that the maximum number of EOL and 
Loudspeaker Supervision boards is not exceeded.
PRS-1P500 can have a maximum of 80 boards, of 
which 16 can be LBB4443/00 EOL boards or 
LBB4441/00 with line supervision enabled.
PRS-2P250 can have a maximum of 40 boards per 
channel, of which 16 can be LBB4443/00 EOL 
boards or LBB4441/00 with line supervision 
enabled.
PRS-4P125 can have a maximum of 20 boards per 
channel, of which 16 can be LBB4443/00 EOL 
boards or LBB4441/00 with line supervision 
enabled.
The multi channel interface can have up to 16 
supervision boards connected to each basic amplifier 
channel of the multi channel interface. The 
maximum number of boards in total across all 
channels is 80, of which 64 can be LBB4443/00 EOL 
boards or LBB4441/00 with line supervision 
enabled. Do not to exceed the maximum number of 
supervision boards related to the maximum output 
power of the amplifier channel; see section 12.6.5.
12.5 Technical 
data 
supervision 
control board
12.5.1 Physical characteristics
12.5.2 Climate conditions
12.5.3 EMC and Safety
12.5.4 Mean time between failure
figure 12.8: ID selectors
Note
The number of EOL supervision boards are 
limited to 16 per channel as the boards are 
polled more frequently than the loudspeaker 
supervision boards to comply to the standards 
for emergency sound systems.
2
E
6
A
8
S701
S700
C
4
2
E
6
A
8
C
4
Dimensions (H x W x D):
60 x 50 x 17 mm
Weight:
30 g
Connection:
20 pole flatband cable and connector
Installation:
Plastic brackets for horizontal or vertical installation 
are delivered with the amplifier.
Temperature:
-5 to 55 °C (operating)
-20 to 70 °C (non-operating)
Relative humidity:
15 to 90%, non-condensing (operating)
5 to 95%, non-condensing (non-operating)
Air pressure:
600 to 1100 hPa
Electromagnetic compatibility:
EN55103-1/FCC-47 part 15B
EN55103-2
EN50121-4
EN50130-4
Electrical safety:
IEC60065 (CB-scheme)
EN60065
Approvals:
CE marking
EN60849, EN54-16 and ISO7240-16
IEC60945
MTBF:
50,000 hours at +55 °C
(The MTBF doubles for every 10 °C decrease in 
temperature.)