Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008
en | 27
EN54-16: 2008 compliancy checklist
Clause / Requirement
Compliance
Signature
4  General requirements
4.1  General
Praesideo is compliant.
4.1.1  If an optional function with requirements is 
included in the VACIE, then all the corresponding 
requirements shall be met (see Annex B).
The following optional functions, with requirements, are included 
in Praesideo from version 3.3 upwards:
• 
Audible warning (7.3) 
• 
Phased evacuation (7.5)
• 
Manual silencing of the voice alarm condition (7.6.2)
• 
Manual reset of the voice alarm condition (7.7.2)
• 
Output to fire alarm devices (7.8)
• 
Voice alarm condition output (7.9)
• 
Indication of faults related to the transmission path to the 
CIE (8.3)
• 
Indication of fault related to voice alarm zones (8.4)
• 
Voice alarm manual control (10)
• 
Interface to external control device(s) (11)
• 
Emergency microphone(s) (12)
• 
Redundant power amplifiers (13.14)
The following optional functions with requirements are not 
included in Praesideo:
• 
Delay(s) to entering the voice alarm condition (7.4)
• 
Disabled condition (9)
4.1.2  If functions other than those specified in this 
European Standard are provided, they shall not 
jeopardize compliance with any requirements of this 
European Standard 
Praesideo power amplifiers and basic amplifiers shall not be 
configured to enter the power save mode when mains power 
fails. Although this would save battery power, the amplifier 
supervision and line/loudspeaker supervision is not active in this 
mode, which is a necessity for systems operating in accordance 
with EN54-16.
The Praesideo PC call station shall not be used as an emergency 
call station in systems operating in accordance to EN54-16. A 
PC does not comply with the requirements as set forward by this 
standard.
4.2  Combined VACIE and CIE
When the VACIE and CIE are combined they may 
share common indications, manual controls and 
outputs (see Annex F). In this case, the following shall 
apply: 
a
single fault in the CIE shall not adversely affect 
the mandatory functions of the VACIE; 
b
indication(s) and manual control(s) of the voice 
alarm condition shall be clearly identifiable, with 
the exception of the optional audible warning.
This requirement is not applicable. In Praesideo, the Voice Alarm 
Control and Indicating Equipment (VACIE) is not combined with 
a fire alarm Control and Indicating Equipment (CIE).
4.3  Power supply
Praesideo is compliant.
Power supply equipment, external or included in the 
VACIE, shall comply with the requirements of EN 54-4.
The installer must use power supplies and battery charging 
equipment in accordance with EN54-4, e.g. the Bosch 
PRS-48CH12, with separate wiring for mains (230Vac) and 
battery backup (48Vdc) from the power supply to the Praesideo 
system.
The power supply equipment must be installed in a separate 
cabinet, not shared with the Praesideo system, unless the 
combination of the actual power supply equipment and 
Praesideo system elements in the same cabinet has been 
certified. 
The content of the EN54-16 certification is subject to change. 
The most recent version of this certificate can be found on 
www.boschsecurity.com.
The network controller and all amplifiers are supplied with a 
mains supply and DC backup supply (48V) input. Switch over 
between the both takes place automatically, without any 
interruption or status change other than the power supply related 
indications.
The installer must ensure that the output voltages of the power 
supply equipment do not exceed the specifications of the mains 
and battery inputs of the connected Praesideo equipment.
NOTE - The power supply may be shared with that of 
the fire detection and fire alarm system.
The power supply may be shared with that of a fire detection 
system, but when operated with a battery a new capacity 
calculation is required.