Bosch 3.5 User Manual

Page of 498
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration
en | 349
43.3.4 Audio outputs
Power amplifiers that are configured as spare amplifiers 
do not have the Delay (distance) setting. This setting is 
taken over from the main amplifier that this spare 
amplifier replaces when it becomes active. The output 
configuration of a spare amplifier is only valid when it is 
in spare state.
When the spare amplifier takes over a main amplifier, 
the configuration of the main amplifier is copied. 
Line/Lsp Supervision can be used to supervise the 
interconnection between the spare amplifier and the 
connected main amplifiers.
If the connected main amplifiers use Single Line/Lsp 
Supervision, then the spare amplifier must not use 
Multiple Line/Lsp Supervision, otherwise a conflict will 
arise between both supervision slave boards when the 
spare amplifiers takes over the from the main amplifier.
If the connected main amplifiers use the Multiple 
Line/Lsp Supervision, then the spare amplifier can also 
use Multiple Line/Lsp Supervision.
figure 43.13: Configure power amplifier, step 5
table 43.9: Audio outputs configuration
Item
Value
Description
Output
Unique name for the audio output. The output can be 
enabled and disabled using the checkbox.
Delay
0 to 95108 ms (PRS-1P500)
0 to 47554 ms (PRS-2P250)
0 to 23777 ms (PRS-4P125)
0 to   1479 ms (LBB4428/00)
Sets the loudspeaker alignment time, also presented 
as distance in meters and feet.
Amplifier supervision/
Pilot tone
On, Off
Switches the pilot tone to on (On,) and off (Off). The 
pilot tone is used to supervise the amplifier channel for 
failures and for supervision of the loudspeaker line and 
loudspeakers.
If set to On, the pilot tone enables supervision and an 
internal calibration keeps the pilot tone at an optimum 
level. If the load on the line changes by the addition or 
removal of loudspeakers, the pilot tone stays at the 
optimum level.
GND Supervision
On, Off
Switches ground supervision of the loudspeaker line 
on (On) and off (Off).
Line/LSP Supervision
None
PRS-SVSET (Single)
PRS-SVCO (Multiple)
Sets the type of line or loudspeaker supervision.
Configure supervision 
devices
Opens a screen to configure LBB4441 and LBB4443 
supervision devices (see section 43.3.5).