Praesideo 3.5 | Installation and User Instructions | 3 | Control Equipment
en | 96
5.6 Configuration and operation
5.6.1
Introduction
The next sections give descriptions of the possible 
configuration options. Each description is followed by 
the relevant menu items with detailed instructions per 
menu option. The default values are indicated by an 
asterisk (*) when applicable.
5.6.2
Start-up
When the network controller is (re)started, the display 
shows the name of the unit and the clock (first of the 
status screens).
5.6.3
Status screens
The status screens (see table 5.7) provide general 
information about the network controller.
5.6.4
Emergency menu
The Emergency ... item (see figure 5.12) provides access to 
the emergency menu. This menu is automatically 
activated when the system is put into the emergency 
state. It changes automatically back to the Clock screen 
when the emergency state is reset. The Emergency ... 
menu screen itself shows the name of key that was used 
to activate the emergency state or the IP address of the 
open interface controller that activated the emergency 
state. For example:
In this example, Emergency indicates that the emergency 
state is active and that it was activated by button
CST-EM-PTT.
The menu items in the emergency menu provide 
additional information about the emergency state and 
allow to acknowledge and reset the emergency state (see 
table 5.8). When the emergency state is reset, all 
emergency calls are aborted.
5.6.5
Faults menu
The Faults ... menu (see figure 5.12) provides access to 
the faults menu. This menu is automatically activated 
when there is a fault in the system. Because the number 
of active faults in the system can vary, the item numbers 
in this menu are not fixed. The youngest fault is the fault 
with the lowest number. The maximum number of 
faults is 200.
table 5.7: Status screens
Menu item
Description
Clock
Shows the name of the unit and 
the time and date.
VU Meter
Visual indication of the signal 
strengths on all audio inputs and 
audio outputs of the network 
controller.
Emergency    ...
CST-EM-PTT
table 5.8: Emergency menu
Menu item
Description
1 Date/Time
Date and time on which the 
emergency state was activated.
2 Acknowledge
Acknowledges the emergency 
state.
3 Reset
Resets the emergency state.
Note
When a new fault occurs while another fault is 
being viewed, the item number of the fault that 
is being viewed is automatically incremented. 
For example, when 23 Overload is being viewed 
while a new fault occurs, it becomes 
automatically 24 Overload.
Note
When fault 200 is being viewed while a new 
fault occurs, fault 200 is automatically deleted 
and replaced by the next fault. For example, 
fault 200 is 200 Overload and the next fault is 
199 Gnd Short. Then 200 Overload 
automatically becomes 200 Gnd Short when a 
new fault occurs.