Heat Controller TGC048C-1K-135 User Manual
NOMINAL 3 TONS
Model
TGC036C-1K-120
TGC036C-3K-120
TGC036C-4K-120
Cooling Performance
1
Gross Cooling Capacity Btuh
37400
37400
37400
EER/SEER
2
11.7/13
11.7/13
11.7/13
Nominal CFM/ARI Rated CFM
1200/1200
1200/1200
1200/1200
ARI Net Cooling Capacity Btuh
36000
36000
36000
Net Sensible Capacity Btuh
26400
26400
26400
Net Latent Capacity Btuh
9600
9600
9600
Net System Power kW
3.08
3.08
3.08
Heating Performance (Package Gas/Electric)
3
Heating Input Btuh
120000
120000
120000
Heating Output Btuh
94500
97200
97200
Temperature Rise ºF
50-80
50-80
50-80
AFUE (%)
80
80
80
Steady State Efficiency (%)
81
81
81
Qty of Burners
6
6
6
Qty of Stages
1
1
1
Gas Connection Pipe Size, in.
.5
.5
.5
Compressor
Qty/Type
Outdoor Sound Rating (dB)
78
78
78
Outdoor Coil—Fin Type
Tube Type
Rifled
Rifled
Rifled
Tube Size in. OD
0.375
0.375
0.375
Face Area sq. ft.
16.91
16.91
16.91
Rows / Fins per inch
1/22
1/22
1/22
Indoor Coil—Fin Type
Tube Type
Rifled
Rifled
Rifled
Tube Size in.
0.375
0.375
0.375
Face Area sq. ft.
5.17
5.17
5.17
Rows / Fins per inch
2/17
2/17
2/17
Refrigerant Control
TXV
TXV
TXV
Drain Connection Qty/Size, in.
1/0.75
1/0.75
1/0.75
Outdoor Fan—Type
Qty Used/Diameter in.
1/24
1/24
1/24
Drive Type/Speeds
Direct/1
Direct/1
Direct/1
CFM
3680
3680
3680
Qty Motors-HP
1-1/3
1-1/3
1-1/3
Motor RPM
1075
1075
1075
Indoor Fan—Type
Qty Used/Diameter in.
1/10x10
1/10x10
1/10x10
Drive Type/Speeds
Direct/3
Direct/3
Direct/3
Motor Qty
1
1
1
Motor HP
1/2
1/2
1/2
Motor RPM
1075
1075
1075
Motor Frame Size
48
48
48
Filter—Type
Furnished
Yes
Yes
Yes
(Qty) Size Recommended in.
(2)16x25x1
(2)16x25x1
(2)16x25x1
Refrigerant Charge Oz.
93
93
93
Weights
Net Weight lbs.
543
543
543
Ship Weight lbs.
550
550
550
Notes:
Disposable
Louvered
1/Copeland Scroll
Corrugated
Propeller
Forward Curved Centrifugal
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan
motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units
are certified and rated per ARI Standard 210/240.
2. EER/SEER are rated ARI condition and accordance with DOE test procedures.
3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National
Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each
1000 feet above sea level.
motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units
are certified and rated per ARI Standard 210/240.
2. EER/SEER are rated ARI condition and accordance with DOE test procedures.
3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National
Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each
1000 feet above sea level.
GENERAL DATA
7
Heat Controller, Inc.
-7-