To Turn Off Gas To Unit 
 
 1-  Set thermostat to lowest level. 
 2-  Turn off all electrical power to unit if service is to be 
performed. 
 3-  Honeywell VR8205 series valve: turn knob on gas 
valve 90° clockwise 
  to OFF
 
White Rodgers 36E series valves: turn knob on gas 
valve 180° either way to OFF
 
Robertshaw DER2000 series valves: depress knob 
on gas valve; knob will snap to OFF
 
Heating Sequence of Operation 
 
 1-  When the thermostat calls for heat, the combustion 
air blower starts immediately. 
 
2- Combustion air inducer proving switch proves 
blower operation before allowing power to the 
ignition controller. This switch is factory set and no 
adjustment is necessary. 
 3- After prepurge of approximately 30 seconds, the 
spark ignition is energized and the solenoid valves 
open in the gas valve. 
 4-  The spark then ignites the gas, the ignition sensor 
proves the flame and the combustion process 
continues. 
 5-  In the event that the flame is not detected after the 
first 10-second trial for ignition, the controller will 
repeat steps 3 and 4 an additional two times before 
locking out the gas valve. Ignition control will then 
automatically repeat steps 3, 4, and 5 after 60 
minutes. 
 
To interrupt the 60-minute lockout period, move 
thermostat from “Heat" to “OFF" then back to 
“Heat." Heating sequence then restarts at step 1. 
6-  The burners shall light without noticeable crossover 
delay. There shall be no flame lifting from the burner 
heads, flashback or burning within the burner. The 
flames shall be predominantly blue in color and 
shall be approximately centered in the tubes with no 
apparent impingement taking place. 
 
7- 
The ignition control will energize the fan 
approximately 45 seconds after ignition is 
established. 
 8-  After  the  thermostat  demand is satisfied the gas 
valve is closed; 5 seconds after the demand is 
satisfied the combustion air blower is shut off. 
 9- The control center shall shut off the system fan 
approximately 120 seconds after the gas valve is 
de-energized. 
Ignition Control LED 
 
The ignition control board contains a green LED which 
indicates the following: 
TABLE 5 
IGNITION CONTROL LED 
LED UNIT 
OPERATION 
Slow 
Flash* 
Normal Operation - No call for heat 
Fast 
Flash 
Normal Operation - Call for heat                     
Current signal at FLAME terminal 0.6 to 1.0 microamps
2 Flashes
System lockout - failed to detect or sustain flame     
Current signal at FLAME terminal <0.6 microamps 
3 Flashes
Combustion air inducer proving switch failed closed 
before CAB is energized or failed open after CAB is 
energized  
4 Flashes
High limit or rollout switch open 
5 Flashes
Flame sensed and gas valve not energized 
Steady 
Off 
Loss of power 
Steady 
On 
Ignition control failure 
*When thermostat is placed in continuous fan mode LED will 
slowly flash. 
 
Optional Gas Conversion Kit 
 
A natural to LP/propane gas changeover kit is required 
to convert unit. Refer to the installation instructions 
supplied with the changeover kit for conversion 
procedure.