AIR FOR COMBUSTION 
AND VENTILATION
Continued 
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have a con-
fined or unconfined space.
Space:
 Includes the room in which you will install 
heater plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1.  Determine the volume of the space (length x 
width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example:
  Space  size  20  ft.  (length)  x  16  ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)
 
If  additional  ventilation  to  adjoining  room  is 
supplied with grills or openings, add the volume 
of these rooms to the total volume of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support. 
 
 _______ (volume of space) x 20 = (Maximum 
Btu/Hr the space can support)
 
Example:
 2560 cu. ft. (volume of space) x 20 = 
51,200 (maximum Btu/Hr the space can support)
3.  Add the Btu/Hr of all fuel burning appliances in 
the space.
 
Vent-free heater    ______________ Btu/Hr
 
Gas water heater*    ______________ Btu/Hr
 
Gas furnace 
  ______________ Btu/Hr
 
Vented gas heater    ______________ Btu/Hr
 
Gas fireplace logs    ______________ Btu/Hr
 
Other gas appliances*  + __________ Btu/Hr
 
Total                             = __________ Btu/Hr
 
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors 
and vents to the outdoors.
 
Example: 
 
Gas water heater    ______________ Btu/Hr
 
Vent-free heater      + _____________ Btu/Hr
 
Total                       = _____________ Btu/Hr
40,000
30,000
70,000
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
 _______________Btu/Hr (maximum the space 
 
 
can support) 
 
 _______________Btu/Hr (actual amount of 
 
 
Btu/Hr used)
 
Example:
 
 
51,200 Btu/Hr (maximum the space can support) 
 
70,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space 
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must provide 
additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined 
space, remove door to adjoining room or add 
ventilation grills between rooms. See Ventilation 
Air From Inside Building, page 7.
B.  Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
C.  Install a lower Btu/Hr heater, if lower Btu/Hr size 
makes room unconfined. 
If the actual Btu/Hr used is less than the maximum 
Btu/Hr the space can support, the space is an uncon-
fined space. You will need no additional fresh air 
ventilation.
 
  WARNING:  If  the  area  in 
which the heater may be oper-
ated is smaller than that defined 
as an unconfined space or if the 
building  is  of  unusually  tight 
construction, provide adequate 
combustion and ventilation air 
by one of the methods described 
in the National Fuel Gas Code, 
ANSI Z223.1/NFPA 54 Section 5.3 
or applicable local codes.