APPLI CAT IONS,  ENGIN EE RING AND DE TAI LE D GUIDANCE  ON SYST EMS DE SI GN, I NSTALL ATION  AND PRODUCT  PE RFORMANCE I S AVAIL ABL E  UPO N REQUE ST. ROBERTS GO RDON
®
 PRODUCTS ARE  TO  BE  
INSTAL LE D ONLY I N ACCOR DANCE  WIT H L OCAL  L AW S,  CODES AND RE GULAT IONS, AND  ONLY BY A CONTRACTO R QUALI FIE D IN  THE  INST AL LAT ION AND  SE RVICE  OF GAS-F IRE D HEAT ING E QUIPMEN T.
Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in 
this Section  are schematic only and provide a gen-
eral guideline of where hangers, reflector supports 
and U-clips are to be installed.
To ensure proper expansion and contraction move-
ment of the reflectors, a combination of U-clips and 
reflector supports are used. The positioning of reflec-
tor supports and U-clips depend on the individual 
installation. The following rules must be observed.
2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip
overlap is achieved by either:
a.) both reflectors lay inside a hanger.
(no reflector support needed).
b.) using a reflector support with
loose screws at the reflector
overlap.
3. The remaining reflector overlaps require a non-slip
overlap connection. To affix the reflectors together in
a non-slip overlap either:
a.) use reflector support and tight screws.
b.) if both reflectors lay inside a hanger, u-clips or 
sheet metal screws may be used.
This section of three reflectors joined together must
be affixed to the tube with at least one reflector support
with tight screws.
Reflector
End Cap
U-Clips
1. The first reflector after the burner must be affixed in
the middle of the reflector with a reflector support and
tight screws.
First Reflector
6"
(16 cm)
Overlap must be a
minimum of 6" (16 cm)
Loose screws
loosened 1/16"
(2 mm) to allow
slippage.
Option A
Slip Overlap
Reflector
Support
Option B
Slip Overlap
Reflector
Tight
screws
Option B
Non-Slip Overlap
U-Clip
(2 clips per
non-slip overlap
inside a hanger)
Reflector
Option A
Non-Slip Overlap
Wire Form
Reflector Support
Strap
Tight
Sheet Metal
Screw
Description
Part Number
Reflector Suppor t Package
03050010
Wire Form
91908004
Reflect or Support Strap
03050000
Screw #8 x 3/4
94320812
U-Clip Package
91107720
Reflect or End Cap