Sterling GF-400 User Manual

Page of 28
4
C
E
(Hanging)
1-3/8"
(35)
(Hanging)
G
D
32-1/2"
(826)
11-5/8"
(295)
(Hanging)
H
(Discharge
Opening)
33"
A
B
L
F
(Discharge Opening)
1" (25)
Electrical Control Panel
Gas Valve
D4617
Rear View
Side View
Front View
Flue 
*
Table 1 - Performance and Dimensional Data - Tubular Propeller Unit Heater
 
Unit 
Size 
100 125 150 175 200 250 300 350 400
 PERFORMANCE DATA†
 
Input 
BTU/Hr. 
100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
                   (kW) 
(29.3) 
(36.6) 
(43.9) 
(51.2) 
(58.6) 
(73.2) 
(87.8) 
(102.5) 
(117.1)
 
Output 
BTU/Hr. 
81,000  101,250 121,500 141,750 162,000 202,500 243,000 283,500 324,000
                      (kW) 
(23.7) 
(29.6) 
(35.6) 
(41.5) 
(47.5) 
(59.3) 
(71.2) 
(83.0) 
(95.0)
 
Thermal 
Effi 
ciency 
(%)  81 81 81 81 81 81 81 81 81
 
Free 
Air 
Delivery 
CFM 
1,600 2,200 2,400 2,850 3,200 3,450 5,000 5,600 5,800
                          (cu. m/s) 
(0.756) 
(1.039) 
(1.133) 
(1.346) 
(1.511) 
(1.629) 
(2.361) 
(2.644) 
(2.738)
 
Air 
Temperature 
Rise 
Deg. 
47 42 47 46 47 54 45 47 51
                                     (Deg. C) 
(26) 
(23) 
(26) 
(26) 
(26) 
(30) 
(24) 
(26) 
(28)
  Full Load Amps at 120V  
5.3 
5.8 
5.8 
8.0 
8.0 
8.0 
11.3 
13.5 
13.5
  MOTOR DATA:  Motor HP (Qty.) 
1/10 
1/4 
1/4 
1/3 
1/3 
1/3 
(2) 1/4 
(2) 1/3 
(2) 1/3
                
Motor kW 
(0.080) 
(0.19) 
(0.19) 
(0.25) 
(0.25) 
(0.25) 
(0.19) 
(0.25) 
(0.25)
                
Motor Type 
SP 
PSC 
PSC 
PSC 
PSC 
PSC 
PSC 
PSC 
PSC
                
R.P.M. 
1,050 
1,140 
1,140 
1,140 
1,140 
1,140 
1,140 
1,140 
1,140
                
Amps @ 115V 
4.2 
4.7 
4.7 
5.8 
5.8 
5.8 
9.4 
11.6 
11.6
  DIMENSIONAL DATA  - inches (mm)
  “A” Overall Height to Top of Flue  33-3/4 
33-3/4 
33-3/4 
33-3/4 
33-3/4 
33-3/4 
34 
34 
34
 
 
(857) (857) (857) (857) (857) (857) (864) (864) (864)
 
“B” 
Jacket 
Width 
of 
Unit 
20-3/4 20-3/4 20-3/4 32-3/4 32-3/4 32-3/4 50-3/4 50-3/4 50-3/4
 
 
(527) (527) (527) (831) (831) (831) (1289) 
(1289) 
(1289)
 
“C” 
Width 
to 
CL 
Flue 
13-3/8 13-3/8 13-3/8 19-3/8 19-3/8 19-3/8 28-3/8 28-3/8 28-3/8
 
 
(340) (340) (340) (492) (492) (492) (721) (721) (721)
  “D” Depth to Rear of Housing 
11 
11 
11 
11 
11 
11 
12-1/4 
12-1/4 
12-1/4
 
 
(279) (279) (279) (279) (279) (279) (311) (311) (311)
 
“E” 
Hanging 
Distance 
Width 
18-5/8 18-5/8 18-5/8 30-5/8 30-5/8 30-5/8 48-5/8 48-5/8 48-5/8
 
 
(473) (473) (473) (778) (778) (778) (1235) 
(1235) 
(1235)
 
“F” 
Discharge 
Opening 
Width 
18-3/4 18-3/4 18-3/4 30-3/4 30-3/4 30-3/4 48-3/4 48-3/4 48-3/4
 
 
(476) (476) (476) (781) (781) (781) (1238) 
(1238) 
(1238)
 
“G” 
Depth 
to 
CL 
Flue 
4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 5-1/8 5-1/8 5-1/8
 
 
(121) (121) (121) (121) (121) (121) (130) (130) (130)
 
“H” 
Discharge 
Opening 
Height 
24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2
 
 
(622) (622) (622) (622) (622) (622) (622) (622) (622)
 
“L” 
Overall 
Unit 
Width 
25-1/4 25-1/4 25-1/4 37-1/4 37-1/4 37-1/4 55-1/4 55-1/4 55-1/4
 
 
(641) (641) (641) (946) (946) (946) (1403) 
(1403) 
(1403)
 
*Flue 
Size 
Diameter 
in. 
 
5 5 5 5 5 5 6 6 6
                        (Dia.-mm) 
(127) 
(127) 
(127) 
(127) 
(127) 
(127) 
(152) 
(152) 
(152)
  Fan Diameter - in. (Qty.) 
16 
16 
16 
18 
18 
18 
(2) 16 
(2) 18 
(2) 18
 
Gas 
Inlet-Natural 
Gas 
(in.) 
1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4
  Gas Inlet- LP Gas (in.) 
1/2 
1/2 
1/2 
1/2 
1/2 
1/2 OR 3/4 
1/2 OR 3/4 
1/2 OR 3/4 
1/2 OR 3/4
 
Approximate 
Unit 
Weight 
lbs. 
 
133 145 155 191 201 211 307 321 335
                                              (kg) 
(60) 
(66) 
(70) 
(87) 
(91) 
(96) 
(139) 
(145) 
(152)
 
Approximate 
Ship 
Weight 
lbs. 
 
173 185 195 241 251 261 367 381 395
                                              (kg) 
(78) 
(84) 
(88) 
(109) 
(114) 
(118) 
(166) 
(173) 
(179)
DIMENSIONS .XXX STANDARD UNITS
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
Figure 2 - Dimensional Drawing – Tubular Propeller Unit Heater
* For all installations, the fl ue collar is included with the unit and should be fi eld installed per the instructions included with the unit.
†  Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea level; refer to 
local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
  For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be derated to 90% of the normal altitude rating, 
and be so marked in accordance with the ETL certifi cation.
D4617