Appendix A
Sun Fire X4100 M2 and X4200 M2 Rack Mounting Specifications
Sun Fire X4100 M2 and X4200 M2 servers should fit in nearly all 3rd-party racks which meet these criteria:
• Rack has a horizontal opening with unit vertical pitch conforming to ANSI/EIA 310-D-1992 and/or IEC 60927
• Four-post structure (i.e. mounting at both front and rear)
• Distance between front and rear mounting planes is between 610 mm and 915 mm (24 to 36 inches)
• Clearance depth (to front cabinet door) in front of front rack mounting plane is at least 25.4 mm (1 inch)
• Clearance depth (to rear cabinet door) behind front rack mounting plane is at least equal to the cable management arm
• Clearance width (between structural supports, cable troughs, etc.) between front and rear mounting planes is at least 456 mm 
(18 inches)
To permit installation in racks meeting the above criteria, there is only one rackslide and cable management arm set for the Sun Fire 
X4100 M2 and X4200 M2 servers. There is no provision in the slide brackets for mounting to non-standard side planes within rack cab-
inets all mounting is to front and rear planes only.
For reference, most generic 19-inch format racks of 900 mm or greater overall depth can accommodate the Sun Fire X4100 M2 and 
X4200 M2; the systems will fit in some shallower racks, and many at 800 mm without the cable management arm.