Troubleshooting
58
8.0
T
ROUBLESHOOTING
Table 18
Troubleshooting
Symptom
Possible Cause
Check or Remedy
Unit will not start
No power to unit
Check voltage at input terminal block.
Control voltage fuses (at 
transformer) open
Locate and repair short. Replace fuses.
Float switch relay has closed 
due to high water in the 
condensate pan.
Check drain and line. Access through left panel.   Power must be 
cycled at the disconnect to reset. Check return air static pressure is 
less than 0.3" wg.
Jumper not in place
Check terminal 37 and 38 for jumper or N/C contact. Check pins P39-
1 and P39-2 for jumper, or N/C firestat contact. Check pins P40-12 
and 1HWAR-Com for jumper or N/C smoke detector contact.
No cooling
“Cooling” is not displayed at 
the control panel.
Adjust TEMP control setpoint and sensitivity to require cooling.
Short cycle prevention 
control.
Control software delays compressor 3 minutes cooling, from stop to 
start
Compressor contactor not 
pulling in.
Check for 24 VAC 
± 2 VAC at terminals TB2 to TB1 for Compressor 1; 
TB6 to TB5 for Compressor 2. If voltage, check contactor. If voltage, 
check freeze stat (FR1 and FR2).
Compressor high head 
pressure.
See below for cause.
Plugged filter/dryer.
Replace filter/dryer.
Low refrigerant charge.
Check pressure gauges. At low ambient temperatures, proper 
refrigerant charge is very important on units with Lee-Temp receivers.
Compressor high 
head pressure
Insufficient air flow across 
condenser coil
Remove debris from coil and air inlets.
Water/Glycol-Cooled only: 
No fluid flowing through 
condenser.
Check fluid supply to regulating valve. Adjust valve if necessary.
Condenser fan not operating
Check fan operation.
Humidifier does 
not operate
DIP switch not set to enable 
humidifier option
See DIP switch settings Table 17.
“HUMIDIFY” not displayed 
at control panel
Increase humidity control setpoint and sensitivity to require 
humidification. 
Defective board
Check voltage at 35-1 and 35-5 on interface board for 24 VAC 
±2 
VAC. If no voltage, check wiring and/or replace board. Check wiring 
from control panel to board.
Failed humidity sensor
Humidity display will indicate dashes. Check wiring from temperature/
humidity board to the control board and from the wall box to the 
control board. Replace wallbox or temperature/humidity circuit board 
(if remote).
No water flow
Make sure switch is in Run position. Check humidifier water supply 
(including filter screen) and check nylon overflow line if canister is full.
Canister fill rate is not 
keeping up with the steam 
output
Check fill valve screen opening and capillary tube for obstructions. 
Check water supply pressure (minimum 10 psig). 
Reheat will not 
operate
DIP switch not set to enable 
reheat option
See DIP switch settings Table 17.
“HEAT” not displayed at the 
control panel
Increase temperature setpoint to require heating.
Reheat safety open, 
defective reheat contact or 
defective board
Check voltage at P34-4 or P34-6 to P34-10 on interface board for 24 
VAC 
± 2 VAC. If voltage, check reheat contactor and reheat safety. If 
no voltage, check wiring and/or replace board. 
Element is burned out
Turn off power. Check element continuity with Ohm meter.