COMMON VENTING OF MULTIPLE HEATERS IN CONFINED SPACES IS 
PROHIBITED.  If any heater connected to a common vent system for 
multiple heaters is found inoperative, the heater should be 
disconnected from the vent system and its entrance into the vent 
system capped. 
Multiple Heater Horizontal venting arrangement. 
 
4” Diameter
single wall Vent
Flue Collar
adaptor
Plan View
Vent Cap
(Breidert or
equivalent Type L)
2” (5cm)
Clearance
Thimble
1/2” (12mm) fall per 20 ft
(6m) toward vent terminal
6” (15cm)
minimum
Swept Tee
4” Diameter
single wall Vent
Flue Collar
adaptor
2” (5cm)
Clearance
Thimble
1/2” (12mm) fall per 20 ft
(6m) toward vent terminal
6” (15cm)
minimum
Swept Y
See multiple
vent size table
for diameter
See multiple
vent size table
for diameter
 
 
VENT SIZING TABLE  —  Multiple Heater Venting 
Number of Heaters 
Horizontal and vertical 
Vertical Only 
 
1 2  3  4 
PTS/U 40/25 
4” 4”  4”  4” 
PTS/U 50/30 
4” 4”  4”  5” 
PTS/U 75/50 
4” 4”  5”  6” 
PTS/U 100/65 
4” 5”  6”  6” 
PTS/U 125/80 
4” 5”  6”  7” 
PTS/U 150/100 
4” 6”  7”  7” 
PTS/U 175/110 
4” 6”  7”  8” 
PTS/U 200/125 
4” 6”  7”  8” 
 
 
COMMON VENT DIAMETER 
(If a size is not available use the next larger size.) 
 
B. 
INDIRECT VENTING    (UNVENTED HEATERS)   —   This heater requires ventilation in the building to dilute the 
products of combustion and provide fresh air for efficient combustion.  Where unvented heaters are used, gravity 
or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr input of installed 
heaters.  Exhaust vents must be located at the highest point above and in the vicinity of the heaters, and the inlet 
vents must be located below the level of the heaters.  An exhaust hood (Part #42924000) must be placed on the 
flue adapter collar located on the end of the last body section when used unvented and must be mounted only in 
an downward position as shown. 
Flue Adapter
Collar
#10 Self-Drill
Screws
(typical)
4” (10cm) Exhaust hood PN 42924000
(point down away from ceiling)