Essick Air AS15012 User Manual

Page of 16
110526
2
Safety Rules
1. Read instructions carefully.
2. Disconnect all electrical service that will be used for the unit 
before you begin the installation.
3. Electrical hook up should be done by a qualifi ed electrician, so 
that all electrical wiring will conform to your local standards.
4. For maximum safety, make sure cooler cabinet is properly 
grounded to a suitable ground connection.
5. Cooler must be connected to proper line current, voltage and 
cycle, as stamped on cooler motor and pump motor specifi cation 
plate.
6. Do not allow pump to tip over and become submerged.
7. Always TURN OFF POWER before performing any mainte-
nance.
Operation
For the best cooling performance, if the pads are dry, pre-wet the pads 
by running the pump for a few minutes before starting the blower.
These coolers may also be used without water for ventilation purposes.  
When outside air is cool (for example, at night) or when humidity is 
high the water pump can be turned off.
Important:  To cool effi ciently, you must exhaust the stale or used air 
from the building.  Open windows or doors or use exhaust fans located 
away from the cooler and in the direction you wish to cool the air.  The 
air will fl ow in the direction of the exhaust openings.  A common guide 
for the amount of exhaust opening needed is to have at least 2 square 
feet of opening per 1000 CFM.
Installation
CAUTION:  Make sure that the mounting surface is strong 
enough to support the operating weight of the cooler when in use.  
(For operating weight, see the general specifi cation table.)
CAUTION:  Do not start cooler until installation is complete 
and unit has been tested for rigidity.
CAUTION:  Make sure all bolts are securely tightened before 
starting the cooler.
• Wet sections.  The wet sections are bolted to the blower section using 
the connector brackets, lift brackets and bolts provided.  Match the 
colored dots on the wet section to the appropriate dot on the blower 
section to insure correct installation.
• Ductwork.  See the General Specifi cation table for dimensions of 
duct opening.  For down discharge units, the duct must go inside 
the opening.  Size these ducts slightly smaller than the duct opening 
in the cooler.  The side and up discharge units have a 1 inch fl ange.  
Size these ducts larger than the duct opening to fi t over the fl ange of 
these units.
Note:  Curbs are not provided.  The installer is responsible for 
providing curbs or other means to support the cooler.
Motor Installation
•  Motor mounting.  Slide the 
heads of the provided carriage 
bolts into the slots of the ad-
justable channels.  Slide these 
channels sideways in the slotted 
holes to align with the holes in 
the motor base and to align the 
motor shaft with the blower 
pulley.  Mount the motor to the 
Water Connections
•  Overfl ow assembly.  Remove nut and place nipple through the hole 
in the pan, with the rubber washer between the pan and the head of 
the drain nipple (Fig. 4).  Screw on  nut 
and draw up tight against bottom of pan.  
Insert overfl ow pipe in nipple to retain 
water.  Overfl ow pipe may be removed 
to drain pan when necessary.  A garden 
hose may be screwed on the drain nipple 
to drain water away from your unit.
•  Pump.  The pump must be secured to prevent it form tipping over.  
Secure the pump to the pump mounting bracket (item 16 in parts 
drawing). Remove a nut located under the head of the pump, place the 
pump bolt though the hole in the mounting bracket, and secure with 
the nut that was previously removed.  Plug pump into receptacles.  
Retain pump cords to internal braces to prevent cords from dropping 
into water reservoirs or contacting moving components.
•  Supply water.  Run a water supply line to the unit.  Each wet section 
requires a 3/8 inch tube connection to the fl oat valve.  The double 
inlet units will have two fl oat valves, one for each wet section.  Note:  
Do not use water supplied from a water softener.
•  Float valve.  Refer to Fig. 5 to install fl oat.  Remove items 1, 2, 
3, and 4.  Insert fl oat body (5) through hole in splash plate (9) and 
back post panel as shown.  Install washer (1) and nut (2).  Tighten to 
motor mount using these carriage bolts 
and the washers and nuts provided 
(see Fig. 1).  Make sure all bolts are 
securely tightened.
•  Motor pulley.  Install the motor pulley 
so that it aligns with the blower pulley 
(see Fig. 2) and tighten set screw.  See 
page 3 for instructions on adjusting pulley.
Electrical Connection
NOTE:  Local building code regulations must be observed.
WARNING:  Disconnect all electrical services that are used for 
this unit before beginning any service to the cooler.
•  Electrical supply.  Cooler must be supplied with the proper line 
current, voltage and frequency, as stamped on blower motor and 
pump motor specifi cation plate.  See the wiring diagrams on page 
4 for typical electrical connections.  Note:  Connecting improper 
voltage to motor will void motor warranty.
•  Wire sizing.  The conductor sizes are to be determined by motor 
loads and length of run per national and local electrical codes.
•  Switches or contactors.  Motors  require switches or contactors of 
proper current capacity and should be sized and installed by a quali-
fi ed electrician.
•  Wiring.  The electrical junction box 
is located in the upper inside of the 
divider channel.  Remove the two 
screws and pull the box out from the 
channel to access wiring (Fig. 3).  
Connect the pump supply wiring to 
the pump receptacles (See the pump 
wiring diagrams on the next page).  
Connect the motor supply wiring 
directly  to the blower motor.
WARNING:  Make sure that cooler cabinet is properly grounded 
to a suitable ground connection for maximum safety.
Fig. 1
Blower 
Housing
Motor 
Pulley
Blower 
Pulley
Fig. 2
Screws
Junction Box
Fig. 3
Rubber Washer
Overfl ow Pipe
Nipple
Bottom Pan
Nut
Fig. 4