APC ACSC100 User Manual
11
InRow SC Operation
General Configuration
The cooling group configuration options are set during the commissioning of the cooling units in the
cooling group.
cooling group.
Caution: This procedure must be performed by APC authorized personnel only. Changing
the settings incorrectly can cause malfunctions to your cooling unit.
the settings incorrectly can cause malfunctions to your cooling unit.
Cooling unit configuration
Path: Main > Configure Unit > General
Use the General menu to set the following:
Start-up Delay.
The delay begins when the cooling unit is started and initialized. The cooling unit
cannot begin operation until this delay expires. Use the start-up delay to restart equipment sequentially in
your room after a scheduled downtime.
your room after a scheduled downtime.
Idle On Leak.
When set to Yes, the cooling unit will enter idle mode if a Water Detection Fault
activates. Set to No to disable the cooling unit from entering idle mode if a leak is detected.
Note: The leak sensor (APC part number AP9325) is optional.
Note: There are three alarms that will cause the cooling unit to enter idle mode:
Note: There are three alarms that will cause the cooling unit to enter idle mode:
• Water Detection Fault (when Idle On Leak is set to Yes)
• Condensate Pump Fault
• Cooling Failure
• Condensate Pump Fault
• Cooling Failure