APC ACSC100 User Manual

Page of 52
InRow SC Operation
16
Run hours
Path: Main > View Run Hours
The cooling unit records the number of hours each of its components has operated. When a component is 
replaced, use the Reset option to reset the run hours for the displayed component to zero.
Path: Main > View Run Hours > Air Filter
•  Air Filter
•  Reset Run Hours
Path: Main > View Run Hours > Fans > Condenser
•  Fan n (n = 1, 2, or 3)
•  Reset Run Hours
Path: Main > View Run Hours > Fans > Evaporator
•  Fan n (n = 1, 2, or 3)
•  Reset Run Hours
Path: Main > View Run Hours > Compressor
•  Compressor
•  Reset Run Hours
Path: Main > View Run Hours > Condensate Pump
•  Conds Pump (Condensate Pump)
•  Reset Run Hours
Path: Main > View Run Hours > Fan Power Supplies
•  LT Fan PS (Left Fan Power Supply)
•  RT Fan PS (Right Fan Power Supply)
•  Reset LT PS Hours (Reset Left Fan Power Supply Hours)
•  Reset RT PS Hours (Reset Right Fan Power Supply Hours)
Thresholds
Set alarms to alert you when components require service or there are high temperature violations.
Path: Main > Set Unit Thresholds
When the air temperature exceeds the temperature defined by the High Temperature Threshold, an 
alarm will occur. Set High Temperature Thresholds for the following:
•  Rack Inlet: An alarm condition exists when the temperature of the air entering the rack at the rack 
inlet sensor exceeds the threshold.
•  Supply Air: An alarm condition exists when the temperature of the air output from the cooling 
unit exceeds the threshold.
•  Return Air: An alarm condition exists when the temperature of the air entering the cooling unit at 
the temperature sensor exceeds the threshold.