InRow SC Operation
40
Troubleshooting
Problem 
Possible Cause
Corrective Action
Fans fail to start
• Cooling Unit shutdown due 
to an external command
• Temporarily remove the user contact cable, if it is 
connected.
• Single fan fails to start
• Confirm that the fan is seated properly and fully engaged. 
• Replace the fan if it is faulty.
Cooling unit cannot 
achieve setpoint
• Improper placement of 
remote temperature sensor
• Verify that the remote temperature sensor is properly 
located in the IT rack.
• Dirty filter
• Clean the filter.
• Dirty coil
• Clean the coil.
• Application error
• Contact APC Worldwide Customer Support at a number on 
the back cover of this manual.
• Heat load is too far away
• Place the cooling unit closer to the heat load.
Water carryover
• Improper fan speed selected 
• Select the next highest fan speed setting. For example, 
change the fan speed setting from Low to Med/Low.
• Room humidity is too high
• Adjust setpoint on dehumidifying equipment.
• Add additional dehumidifying equipment.
• Dirty coil
• Clean the coil. 
• Dirty filter
• Clean the air filter.
• Room humidity is too high
• Adjust setpoint on dehumidifying equipment.
• Improve room sealing.
Cooling unit noise 
level is higher than 
expected
•  Improper fan speed selected
• Select a lower fan speed.
• Incorrect placement of rack 
inlet sensor
• Verify that the rack inlet sensor is properly located in the 
cold aisle.
Temperature control 
not precise enough
• Improper placement of 
remote temperature sensor
• Verify that the remote temperature sensor is properly 
located in the IT rack.
Water outside of 
Cooling unit
• Condensate drain hose is not 
connected or not properly 
routed outside the cooling 
unit
• Verify that the condensate drain hose is properly connected 
to the pump and properly routed outside of the cooling unit.
• Verify that the condensate drain line does not exceed 4.9 
meters (16.0 feet) lift and 15.2 meters (50.0 feet) horizontal 
run.
• Leak in drain system
• Locate and repair the leak.
• Cooling unit not leveled 
properly
• Adjust the leveling feet of the cooling unit.
• Damaged piping insulation
• Identify damaged area and repair the insulation.