InRow SC Operation
Commissioning
Warning: APC authorized personnel must perform the following procedures.
Electrical Hazard: Perform Lockout/Tagout procedures on the cooling unit before 
servicing the cooling unit. Failure to remove power before servicing this equipment could 
result in serious injury or death. 
After installation is complete, verify that all components are working properly and that the cooling unit 
is ready to begin operation.
Inspection Checklists
Initial inspection checklist
The initial inspection ensures that the cooling unit has been properly installed, the location of the cooling 
unit has been properly prepared, and the cooling unit is free of damage.
Warning: The cooling unit operates under pressure. Take proper safety precautions 
when connecting gauges or servicing piping.
Warning:
 Do not operate the cooling unit with any cover, guard, door, or panel removed 
unless the instructions indicate otherwise. Then, proceed with extreme caution.
Warning: Do not run service utilities in front of the fan outlets.
Caution: The vapor barrier minimizes moisture infiltration. Without a vapor barrier, it will 
be difficult to maintain the humidity in the room.
Caution: Do not introduce unconditioned outside air into the space.
Note: A minimum of 900 mm (36 in) of clear floor space in front of and behind the cooling 
unit is required for service access. To roll the cooling unit out of the row, there must be a 
minimum of 1200 mm (48 in) of clear floor space in front of or behind the cooling unit. 
Out-of-row service requires 760 mm (30 in) of side clearance in addition to the front and rear 
clearance.
Ensure that:
The installation procedure is complete according to the installation manual.
The walls, floor, and ceiling of the room where the cooling unit is located are sealed with a vapor barrier.
There is no evidence of damage to the cooling unit.
The cooling unit is level and joined to the adjacent racks or secured to the floor.
The clearance around the cooling unit is in accordance with local and national codes and regulations as 
well as the installation manual.