InRow RD 10 kW Air Cooled Operation and Maintenance
Maintenance
Monthly Preventive Maintenance
Photocopy the following pages and use them during the maintenance procedures. After they have been 
completed, save them for future reference.
Prepared By: ________________________________
Model Number: ______________________________
Serial Number: _______________________________
Date: ______________________________________ 
Environment
‰ In what type of room is the cooling unit located? 
__________________________________________________
‰ Is the cooling unit maintaining the temperature setpoint? 
___________________________________________________
Temperature setpoint _________________________________
‰ Is there visible damage to the cooling unit (dents, scratches)? 
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
‰ Check for environmental damage (dirt, dust, debris, liquid stains) around the cooling unit installation area. 
____________________________________________________________________________________
____________________________________________________________________
‰ Record the room temperature near the air return of the cooling unit.
Temperature ________________
‰ Record the alarm history for the last month. 
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
Cleanliness
‰ Check the condition of the air filters. Change if necessary. 
‰ Check for accumulation of debris in the drain pan. Clean as required.