Figure 30: Individual Flue Connection Detail
Figure 31: Flue Connection Dimensions
11.3 Outside Combustion Air Supply
Where necessary, clean air may be ducted into the burner 
box through an added spigot on the back of the burner 
box replacing the existing dust arrest baffle plate.
See Page 50, Section 11.1.3 for recommendations on duct 
length. Air duct should be as straight as possible. Do not 
use bends in excess of 45°. Consult the manufacturer if 
more than 2 x 45° offset bends are necessary. The fresh 
air duct must be self supporting.
11.3.1 Air Supply Requirements
When fresh air duct is used, follow one of these rules:
• The flue must penetrate the roof while fresh air can 
penetrate any wall. (
• The flue and fresh air supply must penetrate the 
same roof, at a minimum of 1 m apart. (
• The flue must penetrate 1 m higher than the fresh air 
inlet on the same wall. (
Fan Tube
Flue Pipe
Flue Adapter
Fan Assembly
Screw
(Torque: 2 Nm
18 in lb)
Lockwasher
Nut
Fan Tube
Fan
A
B
C
End of Tube
Heater Model
Fan Model
A
B
C
Part Number
BH 15-30
Torin DSF-133-42
79 mm
95 mm
45 mm
C2374B
BH 35-50
AO Smith JF1G
89 mm
102 mm
51 mm
90710000