Roberts Gorden UHD[X][S][R] 200 User Manual
UHD S
TANDARD
D
UCT
F
URNACE
I
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
10
Vents and air intakes must be adequately
supported so that the heater does not bear the
weight of the pipes.
For vent termination See Page 11, Figure 4 through
Page 14, Figure 9.
supported so that the heater does not bear the
weight of the pipes.
For vent termination See Page 11, Figure 4 through
Page 14, Figure 9.
6.3.1 Standard Vented Heaters
(Models UHD[X][R] 150 - 400)
The vent must be fitted with a low resistance
terminal. See Page 11, Figure 4 through Page 12,
Figure 5. Standard vented heaters do not allow
outdoor air intake for combustion air.
(Models UHD[X][R] 150 - 400)
The vent must be fitted with a low resistance
terminal. See Page 11, Figure 4 through Page 12,
Figure 5. Standard vented heaters do not allow
outdoor air intake for combustion air.
6.3.2 Separated Combustion Heaters
(Models UHD[X]S[R] 150 - 400)
The heaters are designed to be installed as
separated combustion heaters. The vent and air
intake are run as separate pipes to the wall or roof
terminals. See Page 14, Figure 9. As an option, the
vent and air intake are run as separate pipes to a
concentric vent box and a concentric vent/air intake
pipe penetrates the wall or roof. See Page 13,
Figure 8 and Page 14, Figure 9.
For separated combustion installation, the vent and
air intake must be fitted with an individual and
correctly sized sealed system and the vent and air
intake must terminate at approved wall and roof
terminate at approved wall and roof terminals.
Separated combustion units may not be common
vented. See Page 9, Section 6.
(Models UHD[X]S[R] 150 - 400)
The heaters are designed to be installed as
separated combustion heaters. The vent and air
intake are run as separate pipes to the wall or roof
terminals. See Page 14, Figure 9. As an option, the
vent and air intake are run as separate pipes to a
concentric vent box and a concentric vent/air intake
pipe penetrates the wall or roof. See Page 13,
Figure 8 and Page 14, Figure 9.
For separated combustion installation, the vent and
air intake must be fitted with an individual and
correctly sized sealed system and the vent and air
intake must terminate at approved wall and roof
terminate at approved wall and roof terminals.
Separated combustion units may not be common
vented. See Page 9, Section 6.
6.4 Unvented Operation
This heater is not approved to be installed in
residential buildings.
For unvented operation in commercial installations,
sufficient building ventilation must be provided in the
amount of 4 cfm per 1000 Btu/h firing rate (United
residential buildings.
For unvented operation in commercial installations,
sufficient building ventilation must be provided in the
amount of 4 cfm per 1000 Btu/h firing rate (United
States); 3 cfm per 1000 Btu/h firing rate (Canada).
WARNING: Combustion by-products contain a
chemical known to the State of California to cause
cancer and birth defects or other reproductive harm.
chemical known to the State of California to cause
cancer and birth defects or other reproductive harm.
6.5 Horizontal Venting
Horizontally vented heaters must be individually
vented.
vented.
Vent pipe must be sloped ¼" (.6 cm) downward for
every 1' (.3 m). For vent lengths greater than 5' (1.5
m), condensation will form. Insulation is
recommended and condensation drains may be
desired.
every 1' (.3 m). For vent lengths greater than 5' (1.5
m), condensation will form. Insulation is
recommended and condensation drains may be
desired.
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or
noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
Instead of an insulated vent terminal, a listed thimble
(with 2" (5 cm) air gap) may be used with a 4" (10
cm) vent cap (P/N 90502102).
(with 2" (5 cm) air gap) may be used with a 4" (10
cm) vent cap (P/N 90502102).
6.6 Vertical Venting
Vertically-vented standard-vented heaters can be
common vented (up to four heaters).
For vent lengths greater than 5' (1.5 m),
condensation will form. Insulation is recommended
and condensation drains may be desired. Vent from
the rear of the heater cabinet then run the vent
vertically and use a condensate drain at the bottom
of the vertical vent.
Vent pipe must be sloped 1/4'' (.6 cm) for every
1' (.3 m).
common vented (up to four heaters).
For vent lengths greater than 5' (1.5 m),
condensation will form. Insulation is recommended
and condensation drains may be desired. Vent from
the rear of the heater cabinet then run the vent
vertically and use a condensate drain at the bottom
of the vertical vent.
Vent pipe must be sloped 1/4'' (.6 cm) for every
1' (.3 m).
For 4'' (10 cm), an approved vent cap
(P/N 90502102) must be used.
(P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502103) must be used.
(P/N 90502103) must be used.
For common vertical venting of more than two
heaters, See Page 12, Figure 6.
heaters, See Page 12, Figure 6.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.
highest point where it passes through a flat roof of a
building.
6.7 Length Requirements
If using vent lengths greater than 5' (1.5 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required.
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required.
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed in buildings with
ventilation rates as per
section 6.4.
Failure to follow these
instructions can result in
death or injury.