For PSC systems, the ½ hp motor is equipped with 4 speeds. The unit is set for mid-fire temp rise @ 
66ºF. See table for proper blower motor set up: 
 
OH6FA072D48 
 
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE 
COOLING UNIT 
 
 
HTG Speed by Input    
    Low                Mid             High 
     Fire                Fire            Fire 
      Recommended CLG Speed  
24,000 
Low 
ML 
MH 
Low 
30,000 
Low 
ML 
MH 
Med Low 
36,000 
Low 
ML 
MH 
Med High 
42,000 
Low 
ML 
MH 
Med High 
48,000 
Low 
ML 
MH 
High 
 
 
 
 
 
Figure 19A:  Heating speed by input 
 
 
Speed Tap\ Static 
Pressure 
Furnace Airflow (CFM) vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
930 
915 
912 
910 
822 
774 
730 
ML 
1155 
1152 
1130 
1126 
1085 
1042 
920 
MH 
1442 
1432 
1418 
1382 
1334 
1293 
1230 
High 
1802 
1762 
1705 
1635 
1569 
1493 
1428 
 
Furnace Motor Current Draw (Amps) vs. External Static pressure (in. WC.) 
Low 
3.3 
3.1 
3.0 
2.9 
2.6 
2.5 
2.4 
ML 
4.2 
4.0 
3.9 
3.7 
3.6 
3.3 
3.0 
MH 
5.4 
5.2 
5.0 
4.7 
4.4 
4.2 
4.0 
High 
6.6 
6.4 
6.0 
5.7 
5.5 
5.2 
5.0 
 
 
 
 
 
 
 
 
Speed Tap\ Static 
Pressure 
High Fire Temperature Rise vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
90 
91 
91 
92 
101 
108 
114 
ML 
72 
72 
74 
74 
77 
80 
91 
MH 
58 
58 
59 
60 
62 
64 
68 
High 
46 
47 
49 
51 
53 
56 
58 
 
 
 
 
 
 
 
 
Speed Tap\ Static 
Pressure 
Mid Fire Temperature Rise vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
72 
73 
73 
73 
81 
86 
91 
ML 
58 
58 
59 
59 
61 
64 
72 
MH 
46 
47 
47 
48 
50 
52 
54 
High 
37 
38 
39 
41 
42 
45 
47 
 
 
 
 
 
 
 
 
Speed Tap\ Static 
Pressure 
Low Fire Temperature Rise vs. External Static pressure (in. WC.) 
0.1 
0.2 
0.3 
0.4 
0.5 
0.6 
0.7 
Low 
60 
61 
61 
61 
68 
72 
76 
ML 
48 
48 
49 
49 
51 
53 
60 
MH 
39 
39 
39 
40 
42 
43 
45 
High 
31 
32 
33 
34 
35 
37 
39