The normal operational sequence in heating mode is as fol-
lows:
R and W1 (or R and W1/W2) thermostat contacts close,
initiating a call for heat.
Integrated control module performs safety circuit checks.
Induced draft blower is energized on high speed for a 15-
second prepurge.  Humidifier terminal is energized with
induced draft blower.
Induced draft blower steps to low speed following
prepurge.  Low stage pressure switch contacts are
closed.
Igniter warm up begins upon step to low speed and
presence of closed low stage pressure switch contacts.
LED LED 
Status 
Indication 
Possible Causes 
Corrective Action(s) 
Notes & Cautions 
Off 
x Normal condition 
x None 
x None 
x None 
1 Flash 
x Communications 
Failure 
x Communications 
Failure 
x  Depress Learn Button 
x  Verify that bus BIAS 
and TERM 
dipswitches are in the 
ON position. 
x Depress once 
quickly for a power-
up reset 
x  Depress and hold 
for 2 seconds for 
an out-of-box reset 
Red 
Communications 
LED 
2 Flashes 
x Out-of-box reset 
x  Control power up 
x Learn button 
depressed 
x None 
x None 
Off 
x No power 
x Communications 
error 
x  No power to furnace 
x Open fuse 
x Communications error 
x  Check fuses and 
circuit breakers; 
replace/reset 
x  Replace blown fuse 
x  Check for shorts in 
low voltage wiring in 
furnace/system 
x  Reset network by 
depressing learn 
button 
x  Check data 1/ data 2 
voltages 
x Turn power OFF 
prior to repair 
1 Steady 
Flash 
x  No network found 
x Broken/ disconnected 
data wire(s) 
x  Furnace is installed as 
a legacy/ traditional 
system 
x Check 
communications 
wiring (data 1/ data 2 
wires) 
x Check wire 
connections at 
terminal block 
x Verify furnace 
installation type 
(legacy/ traditional or 
communicating) 
x  Check data 1/ data 2 
voltages 
x Turn power OFF 
prior to repair 
x Verify wires at 
terminal blocks are 
securely twisted 
together prior to 
inserting into 
terminal block 
x  Verify data1 and 
data voltages as 
described above 
Rapid 
Flashing 
x Normal network 
traffic 
x  Control is “talking” on 
network as expected 
x None 
x None 
Green Receive 
LED 
On Solid 
x  Data 1/ Data 2 
miss-wire 
x  Data 1 and data 2 
wires reversed at 
furnace, thermostat, 
or CT™ compatible 
outdoor AC/HP 
x  Short between data 1 
and data 2 wires 
x  Short between data 1 
or data 2 wires and R 
(24VAC) or C (24VAC 
common) 
x Check 
communications 
wiring (data 1/ data 2 
wires) 
x Check wire 
connections at 
terminal block 
x  Check data 1/ data 2 
voltages 
x Turn power OFF 
prior to repair 
x Verify wires at 
terminal blocks are 
securely twisted 
together prior to 
inserting into 
terminal block 
x  Verify data1 and 
data voltages as 
described above 
 
N
ORMAL
 S
EQUENCE
 
OF
 O
PERATION
P
OWER
 U
P
The normal power up sequence is as follows:
115 VAC power applied to furnace.
Integrated control module performs internal checks.
Integrated control module displays 
88888     88888 on dual 7-segment
display LED’s.
Integrated control module monitors safety circuits
continuously.
Furnace awaits call from thermostat. Dual 7-segment
LED’s display 
00000     PPPPP while awaiting call from thermostat.