Sterling 882.00295.00 User Manual

Page of 72
Large Dehumidifying Dryers  
Controls 
47 
          (System Backup Screen) 
 
                 
 
 
ACS Dryer control version 2.000 introduces a system backup feature.   
 
Pressing SAVE SETTINGS will save the system variables for later recall.   
 
Pressing RESTORE SETTINGS will restore previously saved values.   
 
Pressing RESTORE FACTORY DEFAULTS will return the dryer to its factory default 
state, namely: 
CONVEYING: 
NO CONVEYING UNITS AVAILABLE - CONVEYING DISABLED 
 
 
DRYER OPTIONS: 
TEMPERATURE IN FAHRENHEIT 
STANDARD HEAT 
OVERDRY PROTECTION DISABLED 
AUTO START TIMER DISABLED 
DRYER VALUES: 
ALARM SILENCE DURATION 
 
     99 MIN 
PASSWORD - OPERATOR   
 
          0000 
 
PASSWORD SUPERVISOR  
 
          1234 
PASSWORD OPERATOR DURATION 
     10 MIN 
PASSWORD SUPERVISOR DURATION 
     10 MIN 
DEWPOINT HIGH LIMIT ALARM VALUE        30 DEGF 
 (ALARM DISABLED) 
OVERDRY SET BACK TEMPERATURE 
  170 DEGF 
OVERDRY SET BACK SETPOINT                    100 DEGF 
OVERDRY SET UP TEMPERATURE  
    90 DEGF 
PROCESS AIR TEMP. SETPOINT 
                  180 DEGF 
PROCESS AIR HI DEVIATION VALUE 
    35 DEGF 
PROCESS AIR LO DEVIATION VALUE 
   -35 DEGF 
REGENERATION AIR SETPOINT                    450 DEGF 
PROCESS ACTUAL VALUE OFFSET 
   0.0 DEGF 
REGEN ACTUAL VALUE OFFSET                     0.0 DEGF 
 
                SERVICE   
         (Service Menu Screen)