GE ADER40 User Manual

Page of 36
8
Troubleshooting tips…
Save time and money! Review the chart below first and you may not need to call for service.
Problem 
Possible Causes 
What To Do
Dehumidifier  
The dehumidifier  
Make sure the dehumidifier’s plug is pushed completely 
does not start 
is unplugged. 
  into the outlet.
 
The fuse is blown/circuit 
 Check the house fuse/circuit breaker box and replace
 
breaker is tripped. 
  the fuse or reset the breaker.
 
Dehumidifier has reached its    The dehumidifier automatically turns off when either
 
preset level or bucket is full.   
condition occurs. Change to a lower setting or empty 
 
 
  the bucket and replace properly.
 
Bucket is not in the  
 The bucket must be in place and securely seated for the 
 
proper position. 
  dehumidifier to operate. 
 
Power failure. 
 There is a protective time delay (up to 3 minutes) to 
 
 
  prevent tripping of the compressor overload. For this  
 
 
  reason, the unit may not start normal dehumidifying  
 
 
  for 3 minutes after it is turned back on.
Dehumidifier does not 
Did not allow enough time  
 When first installed, allow at least 24 hours to maintain 
dry the air as it should 
to remove the moisture.   
the desired dryness.
 
Airflow is restricted.  
 Make sure there are no curtains, blinds or furniture 
 
 
  blocking the front or back of the dehumidifier. See the  
 
 
  Choosing a Location section.
 
Dirty filter. 
 See the Care and Cleaning section.
 
The Humidity Control may  
 For drier air, press the 
▼ pad and set to a lower percent   
 
not be set low enough.   
value (%) or at CO (continuous) for maximum   
 
 
  dehumidification.
 
Doors and windows may not  
 Check that all doors, windows and other openings 
 
be closed tightly.  
  are securely closed.
 
Clothes dryer may be  
 Install the dehumidifier away from the dryer. 
 
blowing moisture-laden   
The dryer should be vented to the outside. 
 
air into the room. 
 
Room temperature  
 Moisture removal is best at higher room temperatures. 
 
is too low.  
  Lower room temperatures will reduce the moisture   
 
 
  removal rate. Models are designed to be operated at   
 
 
  temperatures above 41°F (5°C).
Dehumidifier runs 
Area to be dehumidified  
 The capacity of your dehumidifier may not be adequate. 
too much 
is too large.  
 
 
Doors and windows are open.  
 Close all doors and windows to the outside. 
Frost appears on  
Dehumidifier has been turned  
 This is normal. Frost will usually disappear 
the coils 
on recently, or room temperature    within 60 minutes. See the Automatic Defrost section.
 
is below 41°F (5°C). 
Controls cannot be set 
The compressor will turn off  
 This is normal. Wait approximately 3 minutes and set the 
 
and the fan will automatically   fan as desired.
 
continue to run for 
 
approximately 3 minutes at a 
 
fixed setting. 
Fan noise  
Air is moving through 
 This is normal. 
 
the dehumidifier.  
 
Water on floor 
Hose connection may be loose.   Check the hose connection. See the Removing Collected 
 
 
  Water section. 
 
Intended to use the bucket to  
 Disconnect the hose if using the bucket to collect water. 
 
collect water, but a hose 
See the Removing Collected Water section
 
as attached.
Bucket Full LED light  
Drain hose not tight on fitting 
 Check drain hose connection.
flashing and alarm   
sounds while drain hose   
Drain hose is kinked 
 Ensure the drain hose is pointed straight down to the floor 
is connected 
 
and is not kinked in anyway.
Consumer Support
Troubleshooting Tips
Operating Instructions
Safety Instructions
Troubleshooting Tips
Care and Cleaning
Safety Instructions
Operating Instructions