Heat Controller HAH13XX-00-1A User Manual

Page of 6
 
 
made prior to installing these lines).  For left to 
right applications. 
1.  Remove and set aside front panels. 
2.
  Remove the coil support bracket (4-
screws. 
3.
  Remove horizontal drain pan 
retaining clip (1-screw). 
4.
  Carefully remove coil assembly and 
bottom drain pan. 
5.
  Move horizontal drain pan from left 
hand side of coil to right side. 
6.
  Install modified coil assembly back 
into unit. 
7.
  Reinstall coil support bracket and 
horizontal drain pan retaining clip. 
8.
  Determine drain holes being used and 
reposition knockout caps. 
9.  Reinstall doors. 
CAUTION!  IT IS MANDATORY TO USE AN 
EMERGENCY AUXILIARY DRAIN PAN 
WITH ANY COIL OR AIR HANDLER 
INSTALLED IN AN ATTIC OR ABOVE A 
FINISHED CEIING! 
E.  ELECTRIC FURNACE
Optional electric heating packages are available, see 
the unit label for various sizes. 
* See Electric Heater Kit Specifications Table  
 
F.  POWER WIRING
Refer to the unit’s nameplate for specific electrical 
data.  
CAUTION!  DISCONNECT POWER AT MAIN 
FUSE OR CIRCUIT BREAKER 
DISTRIBUTION PANEL BEFORE WIRING 
UNIT TO PREVENT SHOCK OR FIRE 
HAZARD. 
Use copper conductors only. 
Tighten all wire connectors. Refer to unit nameplate 
for minimum circuit ampacity. For correct wire size, 
refer to the National Electrical Code. Use 75˚C 
minimum wire in unit wiring compartment.  
NOTE:  SEE UNIT FOR COMPLETE WIRING 
DIAGRAM LOCATED ON BLOWER 
HOUSING. 
G.  CONTROL WIRING
 
Field connections are made to the low voltage 
terminal strip.  Consult installation instructions 
provided with accessory items for specific 
information on control wiring. Use 18 AWG 
minimum copper control conductors for control 
wiring up to 50 feet between units. 16 AWG control 
conductors are recommended for lengths up to 100 
feet. Class 2 wiring is acceptable. Do not short 
control leads. Transformer burn-out will result.    Set 
thermostat heat anticipator at 0.15 amps for air 
handler. 
H.  BLOWER MOTOR 
Units are equipped with a three-speed blower motor.  
Two factory-selected motor speed leads are 
connected to the fan relay (FR) to provide automatic 
speed change for heating and cooling airflow 
volumes.  The pre-selected motor speeds would 
normally not have to be changed in the field.  All 
HAH models contain a post purge timer (TDR) that 
delays the blower turning off at the end of the 
cooling cycle, this improves energy efficiency. 
 
Terminal number 4 on the (FR) fan relay is the 
cooling blower speed and terminal number 6 on the 
(FR) is the heating blower speed.  
I.  REFRIGERANT PIPING 
All air handlers have DX refrigerant cooling coils 
installed, liquid and suction piping should be sized in 
accordance with condensing unit manufacturer’s 
recommendations.  An adapter (by others) may be 
required to make the transition between the line set 
and the coil connector.  The evaporator coil has 
sweat copper connections.  The suction line is a 
swaged solder cup connection.  The liquid line 
connection is made to a tail piece portion of the 
TXV.  Remove the nut on the inlet to the expansion 
valve and place it on the tail piece prior to brazing 
the liquid line.  DO NOT connect the tail piece to the 
TXV until the liquid line has been brazed to the tail 
piece.  Refrigerant lines should be soldered with 
silver solder or other high temperature brazing alloy.  
Dry nitrogen must flow through the refrigerant lines 
during the brazing operation to prevent oxidation.   
J  REFRIGERANT FLOW CONTROL 
As shipped, the TXV installed on the A-coil is for the 
nominal capacity of a 13 SEER matched with Heat 
Controller Inc. condensing units.  The TXV is for use 
on an R-22 system.  For other refrigerants, contact 
the factory.  TXV has a built-in check valve for 
reverse flow and is suitable for heat pump operation.  
All are externally equalized with non-adjustable 
superheat and have 15% bleed.  Hard start capability 
for outdoor units is not normally required when a 
15% bleed valve is used.  The external equalizer line 
attached to the TXV has a female flare nut and is 
attached to the suction line at the coil.  Install the 
TXV bulb to the suction line using the bulb clamp 
furnished with the kit.  The bulb should be installed 
on a horizontal run of the suction line if possible.  On 
a line less than 7/8” OD, the bulb may be installed on 
top of the line.  With 7/8” OD or over, the bulb 
should be installed in a position of about 4 or 8 
o’clock.  If the bulb installation is made on a vertical 
run, the bulb should be located at least 6 inches from 
any bend and on the tubing side opposite the plane of 
the bend.  On vertical bulb installations, the bulbs 
should be positioned with the bulb capillary tube at 
the top.  The bulb must be insulated using thermal 
insulation to protect it from the effects of the 
surrounding ambient temperature. 
   
06/06                                                                                                                                                                                            HAHIOM062906 
3 of 6