DH90 Dehumidifier • For HVAC Installer Only
The DH90 plugs into a common grounded 115VAC 
outlet.  The  device  draws  6.2  Amps  under  normal 
operating  conditions.  If  used  in  an  area  which 
may  become  wet,  a  ground  fault  interrupter  (GFI) 
protected circuit is recommended.
ImPORTANT: Do not install the humidistat 
where it may not accurately sense the relative 
humidity such as near HVAC supply registers, 
near exterior doors, on an outside wall, near a 
window, or near a water source. 
Refer  to  Section  6  for  typical  hookup  diagrams. 
Some  of  the  control  wires  leaving  the  DH90  may 
not  be  used  with  certain  installations  and  should 
be left unconnected with wire nuts taped onto the 
stripped ends for safety.
4.3 Condensate (Water) Removal
The  DH90  removes  a  large  amount  of  moisture 
from the air and the device must be connected to 
a drain line that will carry away the excess water. A 
trap in the drain line is recommended and may be 
required by some local codes.
The drain line should be connected to the 3/4" male 
pipe thread adaptor on the front of the DH90.
Care should be taken to install the drain line with 
a continuous slope of 1" per 10' to assure proper 
water removal.
4.4 Ducting
ImPORTANT: When connecting ventilation 
duct, remove the label and 6" round 
insulation plug from the ventilation duct 
opening. If not using ventilation feature, 
leave the insulation intact. 
For the ideal installation, draw air from the central 
part of the home and return it to the isolated areas 
of  the  home  like  the  bedrooms,  den,  utility  room, 
or  family  room.  See  Fig.  1.  Alternative  installation 
option  can  be  completed  by  drawing  air  directly 
from  the  return  ducting  and  distributing  through 
the supply air to the home.
4.4A Fresh Air / Supply Air
ImPORTANT: DO NOT draw air directly from 
the kitchen, laundry, or isolated basement. 
Air  may  be  drawn  from  a  basement  that  is  open 
to the home. All flexible ducting connected to the 
DH90 should be UL listed.
A short piece of flexible ducting on all DH90 duct 
connections  is  recommended  to  reduce  noise 
and  vibration  transmitted  to  rigid  ductwork  in  the 
structure. Ducting the DH90 as mentioned requires 
consideration of the following points:
•  Duct Sizing: For total duct lengths up to 
25', use a minimum 10" diameter round or 
Fresh air intake
Supply air
Ducting to isolated areas
Indoor air
return
W8150
Controller
EARD6 
Motorized
damper
Figure 1: Ducting to isolated areas.