Maintenance 
Warnings and Cautions 
WARNING:  Always disconnect AC power before 
working inside the monitor.  
CAUTION: When working inside the monitor, be very 
careful not to dislodge any electrical wiring or pneumatic 
tubing. The HGMSZ contains sensitive electronic 
components that can be easily damaged. Be careful not 
to touch or disturb any of these components. 
Charcoal Filter 
The charcoal filter (Page 8) removes refrigerant gas from the purge-air stream during the purging process. 
Replace the charcoal filter (P/N 3015-4306) about every 6 months, when a zero filter fault occurs (fault 
code <0100>), or after the monitor itself has been exposed to unusually high levels of refrigerant gas, such 
as after an evacuation alarm. 
Hydrophobic Filter 
The hydrophobic filter (Page 8) prevents water from entering the IR detector. A zone flow fault will occur 
(fault code <0800>) if this filter should become blocked. Replace the hydrophobic filter as required 
(P/N 07-1650). 
Servicing Air Lines 
The gas sample line and optional exhaust line should be checked periodically for obvious signs of kinks, 
damage, and contamination. Replace the tubing as required (P/N 304-2743). 
The gas sample line termination filter should be checked periodically and replaced when there are obvious 
signs of contamination. To service the filter simply remove it from the line and replace it with a new one 
(P/N 3015-3420). 
Fuses 
The HGMSZ is protected from electrical damage by two, 1 A, 250 V, type “F” fuses (Page 8). Carefully 
remove the fuses from their fuse clips and visually inspect each fuse for damage. Replace the fuses as 
required (P/N 04-2620). 
Clock Battery 
The clock battery (Page 8) maintains the correct date and time when AC power is not applied to the 
monitor. Replace this battery about every 2 years (P/N 204-0020). 
Sample Pump 
The sample pump (Page 8) draws the gas sample into the monitor, through the IR detector, and discharges 
the sample out the monitor’s exhaust port. When replacing the pump, remove its inlet and outlet tubing, 
disconnect the AC power wires from the pump itself, and remove pump from monitor. Install a new sample 
pump (P/N 3015-4239).