Bacharach 3015-4256 User Manual

Page of 36
30 
Instruction 3015-4256 
Specifications 
Product Type........................ Multiple refrigerant gas monitoring system for low level continuous monitoring 
of refrigerant gases 
Gas Library.......................... CFC: R-11, R-12, R-113, R-114, R-502 
HFC: R-404a (HP62), R-407a, R-407c (AC9000), R-134a, R-410a (AZ20), 
R-507 (AZ50), R-508b (SUVA95) 
HCFC: R-22, R-23, R-123, R-124, R-401a (MP39), R-402a (HP80),  
R-402b (HP81), R-408a, R-409a, R-500, R-503 
HALON: 1301 
Coverage............................... Single zone 
Measuring Range................. All gases 0 to 1,000 ppm 
Monitoring Distance............ Up to 50 ft (15.2 m) maximum gas-sample line length 
Front Panel .......................... 3 Indicator lights: 
MONITOR ON – Green light ON when the unit is operating normally,  
or flashing during warm-up 
SYSTEM FAULT – Yellow light ON when there is a system fault 
ALARM – Red light ON when the gas level is above an alarm setting 
Alarms.................................. Four SPDT relays are provided (rated 3 A, 240 VAC): 
three assigned to ppm level alarms – one assigned to system faults 
 
Internal audible alarm programmable for any of the following conditions: system 
fault, leak alarm, spill alarm, evacuation alarm, monitoring stopped or off 
Detector Type....................... Infrared, Non-Dispersive 
Sensitivity ............................ All gases 1 ppm 
Accuracy ............................... All gases ±10 ppm from 0 to 100 ppm 
All gases ±10% of reading from 100 to 1,000 ppm 
Response Time/Flow Rate... Dependent on gas-sample line length; 0.25" OD x 0.17" ID tubing: 
Gas-Sample Line
Feet (Meters) 
Response Time
Seconds 
Flow Rate 
ml/min 
 0 
(0) 
675 
 10 
 
(3.0) 
13 
664 
 20 
 
(6.1) 
17 
653 
 30 
 
(9.1) 
22 
642 
 40 
 
(12.2) 
26 
631 
 50 
 
(15.2) 
30 
620 
Temperature Drift............... ±0.8% (R-134a) of reading per °C 
System Noise ....................... Less than 40dB(A) at 10 ft (3 m) 
Conditioned Signal .............. 4–20 mA current loop 
Power Safety Mode.............. Fully automatic system reset; all programmed parameters retained 
Operating Temp................... 32 to 122°F (0 to 50°C) 
Ambient Humidity............... 5% to 90% RH (non-condensing) 
Altitude Limit ...................... 6,562 ft (2,000 m) 
AC Power.............................. 100 – 240 VAC 
Power Consumption ............ 15 Watts 
Size/Weight .......................... 7.4"H x 15"W x 3.3"D / 5 lbs (188 x 381 x 84 mm / 2.27 kg) 
Certification ......................... UL 61010A-1, CAN/CSA 22.2 No. 1010-1B:1997,  
CE Mark (see inside front cover), UL 2075 
Warranty.............................. 2 Years from date of shipment