Sierra Monitor Corporation Gas Detector User Manual

Page of 19
 
Sentry MODBUS I/O Memory Map
 
 
 
March 4, 2005
 
Page
2
  
 
Read Only Parameters 
 Modbus 
Address Parameter Units FIX 
EGU 
 
Discrete 
 
40001:0  
High alarm bits - sensor 1 
 
40001:1  
High alarm bits - sensor 2 
 
40001:2  
High alarm bits - sensor 3 
 
40001:3  
High alarm bits - sensor 4 
 
40001:4  
High alarm bits - sensor 5 
 
40001:5  
High alarm bits - sensor 6 
 
40001:6  
High alarm bits - sensor 7 
 
40001:7  
High alarm bits - sensor 8 
 
40002:0  
Low alarm bits - sensor 1 
 
40002:1  
Low alarm bits - sensor 2 
 
40002:2  
Low alarm bits - sensor 3  
 
40002:3  
Low alarm bits - sensor 4 
 
40002:4  
Low alarm bits - sensor 5 
 
40002:5  
Low alarm bits - sensor 6  
 
40002:6  
Low alarm bits - sensor 7 
 
40002:7  
Low alarm bits - sensor 8 
 
40003:0  
Common (High or low) alarm bits - sensor 1 
 
40003:1  
Common (High or low) alarm bits - sensor 2 
 
40003:2  
Common (High or low) alarm bits - sensor 3 
 
40003:3  
Common (High or low) alarm bits - sensor 4 
 
40003:4  
Common (High or low) alarm bits - sensor 5  
 
40003:5  
Common (High or low) alarm bits - sensor 6 
 
40003:6  
Common (High or low) alarm bits - sensor 7  
 
40003:7  
Common (High or low) alarm bits - sensor 8 
 
40004:0 
Common high alarm, any sensor 
 
40004:1 
Common low alarm, any sensor 
 
40004:2 
Common any alarm, any sensor 
 40004:3 
Calibrate 
mode 
 40004:4 
Trouble 
alarm 
 
40004:5 
Power Flash (Startup mode) 
 
40005:0 
Sensor in calibration – sensor 1 
 
40005:1 
Sensor in calibration – sensor 2 
 
40005:2 
Sensor in calibration – sensor 3 
 
40005:3 
Sensor in calibration – sensor 4 
 
40005:4 
Sensor in calibration – sensor 5 
 
40005:5 
Sensor in calibration – sensor 6 
 
40005:6 
Sensor in calibration – sensor 7 
 
40005:7 
Sensor in calibration – sensor 8 
 
40006:0 
Bits indicating analog value is valid – sensor 1 
 
40006:1 
Bits indicating analog value is valid – sensor 2 
 
40006:2 
Bits indicating analog value is valid – sensor 3 
 
40006:3 
Bits indicating analog value is valid – sensor 4 
 
40006:4 
Bits indicating analog value is valid – sensor 5 
 
40006:5 
Bits indicating analog value is valid – sensor 6 
 
40006:6 
Bits indicating analog value is valid – sensor 7 
 
40006:7 
Bits indicating analog value is valid – sensor 8