Teledyne M300EM User Manual

Page of 398
Advanced Features 
Teledyne API – Technical Manual - Model 300E Family CO Analyzers 
124 
7.1.7.2. iDAS Configuration Using Terminal Emulation Programs 
Although Teledyne API recommends the use of APICOM, the iDAS can also be accessed and configured 
through a terminal emulation program such as HyperTerminal (see example in Figure 7-3)
To do this: 
 
All configuration commands must be created and edited off line (e.g. cut & pasted in from a text file or 
word processor) following a strict syntax (see below for example). 
 
The script is then uploaded via the instruments RS-232 port(s). 
 
Figure 7-3: 
iDAS Configuration Through a Terminal Emulation Program 
Both of the above steps are best started by: 
1. Downloading 
the 
default iDAS configuration. 
2.  Getting familiar with its command structure and syntax conventions. 
3.  Altering a copy of the original file offline. 
4.  Uploading the new configuration into the analyzer. 
NOTE 
The editing, adding and deleting of iDAS channels and parameters of one channel through the front-
panel keyboard can be done without affecting the other channels.  
On the other hand, uploading an iDAS configuration script to the analyzer through its communication 
ports will ERASE ALL DATA, PARAMETERS AND CHANNELS and replace them with the new iDAS 
configuration.  
It is recommended that you download and backup all data and the original iDAS configuration before 
attempting any iDAS changes. 
Refer to the next section, 8. Remote Operation, for details on remote access to and from the M300E/EM 
Analyzer via the instrument’s COMM ports.  
04288D DCN5752