Heat & Glo LifeStyle ST-42TVFL-IPI User Manual
Figure 3. Fireplace Locations and Space
Requirements
Requirements
Clearance Requirements
The top, back, and sides of the fireplace are
defined by stand-offs.
defined by stand-offs.
Minimum Clearances from the Fireplace to
Combustible Materials
Glass
Back of
Metal Ends
Top of
Sides
Floor
Fireplace
of Fireplace
Fireplace
Ceiling
36 inches
0
1/2 inch
1/2 inch
4-1/2 inches
36 inches
(914 mm)
(13 mm)
(13 mm)
(114 mm)
(914 mm)
The clearance to the ceiling is measured from the top
of the unit, excluding any standoffs (see Step 10
Finishing).
of the unit, excluding any standoffs (see Step 10
Finishing).
The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch
(25mm).
extending past the face of the fireplace is one inch
(25mm).
The metal end(s) of these fireplaces may NOT be
recessed into combustible construction.
recessed into combustible construction.
3
Installing the
Fireplace
Fireplace
Step 1
Locating the
Fireplace
Locating the
Fireplace
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
requirements for locating a fireplace within a room.
9
Heat & Glo • ST-42TVFL-IPI • 455-902 Rev. C • 12/07
36"
GLASS
GLASS
1"
TOP
VIEW
36"