NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS  •  MERIT
®
 PLUS DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS
Use only approved vent components (see 
Approved Vent Components on Page 2).
These fireplaces must be vented directly 
to the outside.
The  vent  system  may  not  service  multiple 
appliances, and must never be connected to a 
flue serving a solid fuel burning appliance. The  
vent pipe is tested to be run inside an enclosed 
wall (such as a chase). There is no requirement 
for inspection openings in the enclosing wall at 
any of the joints in the vent pipe. 
Installation of Vent Restrictor
A vent restrictor may be needed with this ap-
pliance, install vent restrictor (provided) in the 
appliance top flue outlet as shown in Figure 18 
(MPDT-3328, MPD-3530, MPD-4035 and MPD-
4540) or rear flue outlet as shown in Figure 19 
(MPD-3530, MPD-4035 and MPD-4540). It is 
held in place by friction, only.
Note: The vent restrictor is included in the 
firebox.
Step 3. PREPARING APPLIANCE VENT 
COLLAR (
MPd-3530/4035/4540 models 
with combined top/rear vent)
Each of the unit’s two vent collars are sealed 
with a cover plate and a seal plate and gasket.  
The cover, and seal plate and gasket must  be 
removed from the vent collar being used. Refer 
to Figure 16 for top vent usage and Figure 17  
for rear, and the following steps to prepare the 
appropriate collar for use.
From the vent collar being used, remove the four 
screws securing the vent seal plate and gasket.  
Remove and discard the seal plate and gasket.
When the top vent collar is being used, from 
inside the firebox, loosen the two screws in the 
keyhole slots of the cover plate and remove the 
remaining  two  cover  plate  securing  screws.  
Remove and discard the cover plate.  Reinstall 
and securely tighten all four screws.
When the rear vent collar is being used, from 
inside the firebox, remove the two screws se-
curing the lintel to the rear wall of the firebox, 
then remove the lintel. Remove the four cover 
plate  securing  screws.  Remove  and  discard 
the cover plate.   
Reinstall  and  securely  tighten  all  four  cover 
plate screws. Re-secure the lintel to the rear 
wall of the firebox. 
Figure 18
VENT SEAL PLATE
GASKET
FIREBOX TOP
CABINET TOP
SECURING
SCREWS
VENT
COVER PLATE
TOP VENT
ON MPD-3530/4035/4540 SERIES MODELS
 (COMBINED TOP AND REAR VENT UNITS)
TOP VENT SEAL & COVER PLATE REMOVAL
WHEN USING THE TOP VENT
COVER PLATE
SECURING SCREWS
CROSS SECTION
(INSIDE UNIT)
(OUTSIDE UNIT)
VENT SEAL PLATE
GASKET
SECURING
SCREWS
CROSS SECTION
LINTEL
SECURING
SCREWS
LINTEL
REAR VENT
COVER PLATE
SECURING SCREWS
ON MPD-3530/4035/4540 SERIES MODELS
(COMBINED TOP AND REAR VENT UNITS)
REAR VENT SEAL & COVER PLATE REMOVAL
WHEN USING THE REAR VENT
CABINET BACK
(INSIDE UNIT)
(OUTSIDE UNIT)
Figure 17
Figure 16
A vent restrictor may be needed when
vertically terminating the vent system above
the roof (when using the appliance top vent),
install vent restrictor in the top vent of the
fireplace outlet on MPD-3530/4035/4540
 and MPDT-3328 series models.
RESTRICTOR
APPLIANCE TOP
VENT OUTLET
VENT RESTRICTOR INSTALLATION
(TOP VENT)
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
INNER
FIREPLACE
 COLLAR
RESTRICTOR
APPLIANCE REAR
VENT OUTLET
A vent restrictor may be needed when
horzontally terminating the vent system from
the rear of the appliance (when using the
appliance rear vent), install vent restrictor in
the rear vent of the fireplace outlet on
MPD-3530/4035/4540 series models, in any
installation that has a vertical vent run in
excess of three feet (0.914 meters).
VENT RESTRICTOR INSTALLATION
(REAR VENT)
INNER FIREPLACE
COLLAR
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
Figure 19
Step 4. INSTALLING VENT SYSTEM
 
These  instructions  should  be  used  as  a 
guideline and do not supersede local codes 
in any way. Install venting according to local 
codes, these instructions, the current National 
Fuel Gas Code (ANSI-Z223.1) in the USA or 
the  current  standards  of  CAN/CSA-B149.1 
in Canada. 
Ensure  clearances  are  in  accordance  with 
local installation codes and the requirements 
of the gas supplier.
dégagement conforme aux codes d'installa-
tion  locaux  et  aux  exigences  du  foumis-
seunde gaz.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, determine 
vent routing and identify the exterior termina-
tion location. The following sections describe 
vertical  (roof)  and  horizontal  (exterior  wall) 
vent applications. Refer to the section relating 
to your installation. A list of approved venting 
components are shown on Pages 34 and 35.
       WARNING 
Failure to reinstall and securely 
tighten cover plate screws could 
result in leakage of flue products 
into the living space.  Vent cover 
plate  and  vent  seal  cap  must 
remain  securely  in  stalled  on 
unused vent collar.  Failure to 
do so could result in leakage of 
flue products into living space.