Regency P42-LP4 User Manual

Page of 48
Regency
®
 P42-4 Zero Clearance Direct Vent Gas Fireplace
14
Rigid Pipe Adaptor
(Part# 510-994)
Pipe Length
Vertical
Terminal
Storm Collar
Part # 953
Flashing
943 or 943S
Ceiling Firestop
(Part # 963)
24" Pipe
Length
Adj.Pipe Length
11" - 14-5/8"
90 Elbow
o
Horizontal
Termination
Cap
Wall Thimble
Part # 942
Vinyl Siding
Standoff (Optional)
Part #950
RIGID PIPE VENTING
Horizontal or Vertical Terminations
The Rigid Pipe Venting System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are 
offered in decorative black, as well as galvanized fi nish. We recommend using the galvanized fi nish for installation with the P42.
The minimum components required for a basic 
horizontal termination are:
 1 Horizontal 
Termination 
Cap
 1 90
o
 Elbow 
 1 Flue 
Adaptor
 1 Wall 
Thimble
  1  Length of pipe to suit wall thickness 
   (see 
chart) 
Alternate 
Horizontal 
Termination Caps
INSTALLATION
   
 Flat Wall Installation
            Wall Thickness         Vent Length
 
(inches)         Required (inches)
 4" 
 
    5-1/2" 
6"
 7" 
    8-1/2" 
9"
 10" 
  11-1/2" 
12" 
 9" 
  14-1/2"        11" - 14-5/8" Adj. Pipe
 15" 
  23-1/2" 
17" - 24" Adj. Pipe
    Corner Installation
            Wall Thickness         Vent Length
                   (inches)         Required (inches)
 3-1/4" 
 
 
   6-3/4"11" - 14-5/8" Adj. Pipe
 7-3/4" 
 16-1/4" 
17" - 24" Adj. Pipe
 7-1/4" 
   8-3/4" 
6" + 12"
  
 
 
9" 
9"
 4-1/4" 
   5-3/4" 
6" + 9"
Wall thickness  is measured from the back 
standoffs to the inside mounting surface of 
termination cap. For siding other than vinyl 
furring strips may be used, instead of the vinyl 
siding standoff, to create a level surface to 
mount the vent terminal. The Terminal must 
not be recessed into siding. Measure the wall 
thickness including furring strips.
If a Vinyl Siding Standoff is required (it must 
be used with vinyl siding), measure to outside 
surface of wall without siding and add 2 
inches.
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be 
used to secure rigid pipe to adaptor.
The FPI AstroCap
TM 
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent
®
 Direct Vent GS, 
American Metal Products Ameri Vent Direct Vent, Security Secure Vent
®
, Selkirk Direct-Temp. AstroCap
TM
 is a proprietary trademark of FPI Fireplace 
Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
This product has been evaluated by Intertek for 
using a Rigid Pipe Adaptor in conjunction with 
Duravent Direct-Vent GS, Selkirk Direct-Temp, 
Ameri Vent Direct venting and Security Secure 
Vent systems. Use of these systems with the 
Rigid Pipe adaptor is deemed acceptable 
and does not affect the Intertek WHI listing of 
components.
WARNING:
Do not combine venting components from 
different venting systems.
However use of the the AstroCap
TM
 and FPI 
Riser is acceptable with all systems.