Regency P48-NG User Manual

Page of 48
Regency P48 Zero Clearance Direct Vent Gas Fireplace
7
INSTALLATION
The  HeatWave Duct Kit
and the Heat Release
Kit have different clear-
ance and framin require-
ments, check the Heat-
Wave
 and Heat Release
manual for details.
Heat Release Kit
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of
the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
Minimum Clearance from Top of Front Facing:
Mantel
min. 8"
(203mm)
Ceiling
39"
(990mm) from top of front facing above louvers.
Side Wall:
6"
(152mm)
Horizontal Vent Clearances:
Top
2-1/2"
(64mm)
Side
1-1/2"
(38mm)
Bottom
1-1/2"
(38mm)
Vertical  Vent  Clearances:
1-1/4"
(32mm)
Alcove Clearances:
Max. Depth
36"
(914mm)
Min. Width
60"
(1524mm)
Min. Height
80"
(2032mm)
Caution Requirements
The top,  back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
fireplace and vent system be installed only in
accordance with these instructions.