Regency P40-NG User Manual
Regency
®
P40 Direct Vent Gas Fireplace
13
INST
ALLA
TION
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
A=
Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)
B=
Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)
C=
Clearance to permanently closed window *#(min. 12"/30cm)
D=
V
ertical clearance to ventilated soffi
t located above the terminal within a horizontal
distance of (24"/60cm) from the centerline of the terminal (min. 23") check with local
code.
E=
Clearance to unventilated soffi
t
(min.
15"/38cm)
F=
Clearance to outside corner: 13"
G=
Clearance to inside corner: 13"
H=
Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally
from the centerline of the regulator
.
J=
Clearance to service regulator vent outlet *(min. 36"/90cm)
K=
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
any other appliance *(12"/30cm) #(9"/23cm)
L=
Clearance to a mechanical air supply inlet *(6'/1.83m)
#3' (91cm) above if within 10' (3m) horizontally
.
M=
Clearance above paved sidewalk or a paved driveway located on public property
*(min. 84"/2.1m)
N=
Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)
Note:
- Excluding direct vent or non-condensing appliances, a vent shall not terminate directly above a sidewalk or paved driveway wh
ich is located between two single family
dwellings and serves both dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl
oor
.
- If the vent termination is accessible, a certifi
ed guard shall be installed.
* (Canada)
As specifi
ed in CGA
B149 Installation Code. Note: Local codes or regulations may require dif
ferent clearances.
# (US) In accordance with the current
ANSI Z223.1/NFP
A
54, Natioinal Fuel Gas Code.