Regency P42-LP3 User Manual

Page of 44
Regency P42-3 Zero Clearance Direct Vent Gas Fireplace
16
The P42 is approved for a  23 ft. (7.0m) vertical, with a maximum 12 ft (3.7m) horizontal offset
using two 90
o
 elbows (two  45
elbows equal one 90
o
 elbow) with rigid pipe vent systems for
Propane and Natural Gas, as per the diagram below.
No Vent restrictor is required.
Vent must be supported at offsets
The P42 is approved for a  37 ft. (11.3m) straight
vertical, with rigid pipe vent systems for
Propane and Natural Gas, as per the diagram
below.
Vent restrictor #6 must be used
Diagram 3
Diagram 4
Note: Regency Direct Vent System (Flex) is only approved for
horizontal terminations.
INSTALLATION