Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
15
INSTALLATION
FLUEING ARRANGEMENTS  -  HORIZONTAL  TERMINATIONS
SIMPSON DURA-VENT DIRECT  VENT GS SYSTEM  (LPG & NG)
The diagram below shows examples of horizontal termination arrangements using one, two, or three 90
o
 elbows (two  45
elbows equal one 90
o
elbow).
Note:
1) A  maximum  of  three  90
o
  elbows  are  permitted.
2) Minimum  distance  between  elbows  is  1  ft.  (305mm).
•
Maintain  clearances  to  combustibles  as  listed  on  page  9.
•
Horizontal  flue  must  be  supported  every  3  feet.
•
Firestops  are  required  at  each  floor  level  and  whenever  passing  through  a  wall.
•
Must  use  optional  flue  adapter  (Part#  510-994)  when  using  Simpson  Dura-Vent  pipe.
•
A  vent  guard  should  be  used  whenever  the  termination  is  lower  than  the  specified  minimum  or  as  per  local  codes.
Simpson  Dura-Vent
4"  inner  diameter
6-5/8"  outer  diameter
Straight Out Horizontal Flueing
Horizontal Flueing with One (1) 90
o
 Elbow
Option
V
H
     A)
1'  (305mm)  Minimum
3'  (914mm)  Maximum
     B)
2'  (610mm)  Minimum
6' (1.86m) Maximum
     C)
3'  (914mm)  Minimum
9' (2.7m) Maximum
     D)
4'  (1.22m)  Minimum
12' (3.6m) Maximum
     E)
5' (1.5m) Minimum
15' (4.5m) Maximum
     F)
6'  (1.86m)  Minimum
17' (5.1m) Maximum
Diagram  1
Diagram  2
With the above options, maximum total pipe length if 37 feet with
minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90
o
 elbows is required.
Please  note  the  minimum  centerline
for  basic  install  shown  above.