Regency P121LC-NG User Manual

Page of 40
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
9
INSTALLATION
COMBUSTIBLE    MANTELS
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams on page 8):
WARNING:
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fireplace
and flue system be installed
only in accordance with these
instructions.
Clearance  to  Combustibles  from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by
standoffs.  The  metal  ends  of  the  standoffs  may  NOT  be  recessed  into  combus-
tible  construction.
Determine  the  total  thickness  of  the  finished  floor  (eg.  tile,  carpet,  slate)  to  allow
the  finished  surface  to  be  flush  with  the  base  of  the  unit.
Ceiling  Height  from  Floor  72"  (1828mm)
Mantel  Height  from  Base  of  Unit:
39" min.  (991mm)
Horizontal  Flue  Clearances:
Top
2-1/2"(64mm)
Side
1-1/2"(38mm)
Bottom
1-1/2"(38mm)
Vertical  Flue  Clearances 1-1/4" (32mm)
Because  of  the  extreme  heat  this  fireplace  emits,  the  mantel  clearanc-
es are critical. Combustible mantel clearances from top of unit are shown in
Diagram to the right.
Note: A  non-combustible  mantel  may  be  installed  at  a  lower  height  if
the  framing  is  made  of  metal  studs  covered  with  a  non-
combustible  board.
This drawing is to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area or higher using this scale.
Caution:  Ensure  the  paint  that  is  used  on  the  mantel  and  the  facing  is
      "heat  resistant"  or  the  paint  may  discolour.
* If the 3"  (76mm) metal extension trim is removed it must be replaced with a 8"
(203mm) non-combustible material.
Mantel  Clearances