Regency P40-LP1 User Manual

Page of 56
Regency
®
 P40-1 Direct Vent Gas Fireplace
9
INST
ALLA
TION
INSTALLATION
CLEARANCES
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest 
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
P40
P40 with Full Screen Front Door
Back
0" (0mm)
0" (0mm)
Side
0" (0mm)
6" (0mm)
Floor
0" (0mm)
0" (0mm)
* Note: A hearth is required, unless the unit is raised
  4" (102mm), see "Hearth Requirements" section for details.
Minimum Clearance from Top of Louver Opening:
Mantel Height min. 12"  (305mm) (at 1" mantel depth) 
Ceiling 39" (990mm) 
Side Wall to Unit:
  
8" 
(203mm)
Horizontal Vent Clearances to Combustibles:
Top 
2-1/2" (64mm)
Side 
1-1/2" (38mm)
Bottom 
1-1/2" (38mm)
Vertical  Vent  Clearances to Combustibles:
All Sides 1-1/4" 
(32mm) 
Alcove Clearances:
Max. Depth 36" 
(914mm)
Min. Width 56" 
(1422mm)
Min. Height 72" 
(1829mm)
Caution Requirements
The top,  back and sides of the fi replace are defi ned by 
standoffs. The metal ends of the standoff may NOT be 
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk 
if these clearances (air space) to combustible materials 
are not adhered to. It is of greatest importance that this 
fi replace and vent system be installed only in
accordance with  these instructions.
WARNING: When installing the Full Screen Doors
The Full Screen Front  requires additional non combustible facing and 
non-combustible framing.  Ensure the 10-1/4" above the fi replace, 6" 
on both sides and both the header and side studs are non-combustible 
materials. All other clearances, including mantel, remain the same.