Regency FP90 User Manual

Page of 40
FPI FP90 Wood Fireplace
9
INST
ALLA
TION
Building Structures Cannot Encroach on Chase
50-3/4"
(1289mm)
44"
(1118mm)
INSTALLATION OF 
NAILING STRIPS
1)  Assemble 3 Nailing Strip Spacer Plates 
to the left and the right Nailing Strips as 
shown below.
Left Nailing Strip
Nailing 
Spacer
Right Nailing
Strip
x 12
Right Nailing Strip
Top Nailing
Strip
Left
Nailing
Strip
x 9
2)  Mount Nailing Strips left, right and top to the 
positions indicated below.
NOTE:
Nailing Strips are adjustable to allow for correct 
offset from the front of the fi replace for your 
current application.
There are two adjustments to allow for maximum 
offset (1" , 25mm recessed from front of fi replace 
or 1.25", 32mm  extending past front of fi replace). 
The Nailing Strip Spacers can be adjusted by 
loosening the two screws securing them to the 
Nailing Strips. The Nailing Strips can also be 
moved forward and back by adjusting the screws 
that mount them to the fi replace.
FIREPLACE 
ENCLOSURE FRAMING
As per the diagram, the framing of the main 
enclosure should not infringe on the area above 
the fi replace to the ceiling level.  The rear and 
side walls as well as the face above the fi replace 
must not extend into the area above the unit. 
The only structure allowed above the unit is on 
the stand-offs at the front of the unit supporting 
the header.
The enclosure walls can be framed using any 
suitable material (2x4 - 2x6 studs, plywood, 
gyproc, etc.), Normally, framing will be set 
back to allow Non-Combustible Material to 
be fl ush with the front of the fi replace.
There is framing only on the front of the unit. 
When framing in the header (directly above 
the fi replace)  DO NOT bring any combustible 
material lower than the top of the stand-offs. 
Framing header may be positioned on end 
directly on top of the front fi replace stand-offs. 
Be sure to seal the space between the fi replace 
and the enclosure above and on either side of 
the unit with Wonderboard, Durock or other 
similar non-combustible sheeting to prevent hot 
air from entering the enclosure.
C A U T I O N :   O N L Y   N O N -
C O M B U S T I B L E   M AT E R I A L 
L I K E   E X PA N D E D   M E TA L  O R 
CONCRETE BOARDS SUCH AS 
WONDERBOARD AND DUROCK, 
ETC. MAY BE USED IN THE 
SPACE BETWEEN THE UNIT AND 
THE FRAMING IN FRONT OF THE 
UNIT ONLY.
Note:   If the fi replace is being cantilevered 
through an outside wall, the entire 
enclosure (floor, wall and false 
ceiling) up to the fi rst ceiling level 
must be completely insulated and 
vapor sealed and sheathed, to avoid 
transfer of cold air through the 
fi replace when not in use.
Framing Specifi cations
INSTALLATION
44 " [1118mm]
" [248mm]
3
4
9
 " [2930mm]
8
3
115
18 " [457mm]
 " [370mm]
8
14
5
28 " [710mm]
 " [1465mm]
 " [2072mm]
81
2
1
8
5
57
4
1
31  " [795mm]
13  " [348mm]
3
4
60 " [1524mm] CHASE
 " [348mm]
3
4
13