RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS  
(Propane & Natural Gas)
The G36D is approved for a maximum 23 ft. (7.0m)  vertical,  with a maximum 12 ft. (3.7m) horizontal offset 
using two 90
o
 elbows (two  45
elbows equal one 90
o
 elbow) with 
Rigid Pipe vent systems for Propane and 
Natural Gas, as per diagram 1.
The G36D is approved for a  maximum 37 ft. (11.3m) straight vertical, including a maximum 20" (0.5m) horizontal 
offset using two 90
o
 elbow (two  45
elbows equal one 90
o
 elbow)  with 
Rigid Pipe vent systems for Propane 
and Natural Gas, as per diagram 2.
•  Vent must be supported at offsets
•  Maintain clearances as listed in the"Clearances" section.
•  Firestops are required at each fl oor level and whenever passing through a wall.
Note:  Must use optional rigid pipe  adaptor when using rigid vent systems (Part # 510-994).
Note:  UltraGlow
®
Note:  UltraGlow
Note:  UltraGlow  Direct Vent System (Flex) is only approved for horizontal terminations.
®
®