Quadra-Fire 7051-158B User Manual

Page of 58
December 6, 2011
7051-158B
Page  41
EDGE 60 Pellet Fireplace
E.  Chimney and Exhaust Connection
1. 
Chimney & Connector:  Use 3 or 4 inch (76-102mm)  
diameter type "L" or "PL" venting system.  It can be vented 
vertically or horizontally.
2. Mobile Home: Approved for all Listed pellet vent.  As 
with all installations a Quadra-Fire Outside Air Kit must 
be used with manufactured home installations.
3
.  INSTALL VENT AT CLEARANCES SPECIFIED BY THE 
VENT MANUFACTURER.
4.  Exhaust Venting System: Secure to the appliance with 
at least 2 screws 180 degrees apart.  Also secure all 
connector pipe joints with at least 3 screws through each 
joint.
NOTE: All pipe must be welded seam pipe whenever 
possible.  Seal pipe joints with high temperature silicone 
(500°F [260°C] minimum rated only).
NOTE:  If burning shelled fi eld corn, you must use 
approved venting specifi cally designed for corn.  Follow 
the instructions from the venting manufacturer.
•  Only LISTED venting components may be used.
•  NO OTHER vent components may be used.
•  Substitute or damaged vent components may impair 
safe operation.
WARNING! RISK OF FIRE!
WARNING! RISK OF INJURY OR PROPERTY 
DAMAGE!
•  Improper installation, adjustment, alteration, service or 
maintenance can cause injury or property damage. 
•  Refer to the owner’s information manual provided with this 
appliance. 
•  For assistance or additional information consult a qualifi ed 
installer, service agency or your dealer.
The table below can help you calculate the equivalent feet 
of pipe which is a method used to determine pellet vent size.  
Figure 40.1.
F.  Equivalent Feet of Pipe
Figure 40.1
2 ft.
2 ft.
3 ft.
2 ft.
Example of 3 Elbow-Rear Vent Termination Calculation
Pellet Venting 
Component
# of 
Elbows
Feet of 
Pipe
Multiplied 
By
Equivalent 
Feet
Components
Equivalent Feet
90
o
 Elbow or Tee
3
X
5
15
45
o
 Elbow
X
3
Horizontal Pipe
7
X
1
7
Vertical Pipe
2
X
0.5
1
Total Equivalent Feet
23
Note:  This is a generic example and is not 
intended to represent any specifi c fuel type.
Vent surfaces get HOT, can cause burns 
if touched.  Non-combustible shielding or 
guards may be required.
WARNING
CAUTION!
• 
DO NOT CONNECT THIS UNIT TO A CHIMNEY 
FLUE SERVING ANOTHER APPLIANCE.
• 
DO NOT INSTALL A FLUE DAMPER IN THE EX-
HAUST VENTING SYSTEM OF THIS UNIT.