Regency G36D-LP PROPANE User Manual

Page of 40
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace
6
INSTALLATION
Diagram 1
This includes:
1)  Clocking the appliance to ensure the correct 
fi ring rate (rate noted on label 26,000 Btu/h) 
after burning appliance for 15 minutes.
2)  If required, adjusting the primary air to ensure 
that the fl ame does not carbon. First allow 
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that 
causes sooting or carboning that results 
in damage is not the responsibility of the 
manufacturer.
LOCATING YOUR 
GAS STOVE
1)  When selecting a location for your stove, 
ensure that the clearances outlined on this 
page are met.
2)  Provide adequate clearances for servic-
ing.
3)  The appliance must be installed on a fl at, 
solid, continuous surface (e.g. wood, metal, 
concrete). This may be the fl oor, or raised up 
on a platform to enhance its visual impact. 
If the appliance is going to be installed on 
carpeting, combustible linoleum tile or other 
combustible material other than wood fl oor-
ing, the appliance must be installed on a 
metal or wood panel extending the full width 
and depth of the appliance.
4)  The G36D Direct Vent Gas Fireplace can be 
installed in a recessed position or framed out 
into the room as in A, B, C, D. See Diagram 
1.
 A) Flat 
on 
Wall
 B) Flat 
on 
Wall 
Corner 
  
C) Recessed 
into 
  
 
 Wall/Alcove
  
D) Corner   
5)  This appliance is Listed for bedroom  instal-
lations when used with a Listed Millivolt 
Thermostat. Some areas may have further 
requirements, check local codes before 
installation.
6)  The G36D Direct Vent Gas Fireplace is 
approved for alcove installations, which 
meet the clearances listed on this page.
7)  We recommend that you plan your instal-
lation on paper using exact measurements 
for clearances and fl oor protection before 
actually installing this appliance. Have a 
qualifi ed inspector, dealer, or installer review 
your plans before installation.
Note:   For vent terminations see page 10.
G36D UNIT DIMENSIONS
MANUFACTURED 
MOBILE HOME
ADDITIONAL 
REQUIREMENTS
1)  Ensure that structural members are not cut 
or weakened during installation.
2)  Ensure proper grounding using the #8 
ground lug provided. See page 29.