10
Vermont Castings Intrepid Multi-Fuel
2000970
Connecting Flue Pipe - Clearances
Single wall connecting fluepipes can reach extremely 
high temperatures; therefore, clearances from the con-
necting fluepipe (chimney connector) must comply with 
the requirements of Part J of Building Regulations 2000 
(Combustion Appliances and Fuel Storage Systems). 
This can be achieved by following the recommenda-
tions of Approved Document ‘J’. These are as shown in 
Figure 11.
ST486a
Defiant EU
Clearance
Diagrams
10/06
A
B
ST486a
Fig. 10  Minimum clearances.
�����
�������������������
�����
D
at least 
3 x D
Elevation 
Without 
Shield
Elevation 
With Shield
at least 
3 x D
at least 
1.5 x D
at least 
1.5 x D
Plan Without 
Shield
Plan With 
Shield
Air space of at least 12 mm 
between noncombustible shield 
and combustible material
Fluepipe
at least 
1.5 x D
at least 
1.5 x D
at least 3 x D
D
at least 
1.5 x D
ST911
Fig. 11  Connecting fluepipe clearances.