Procom ML200HBA User Manual

Page of 21
5
       WARNING:   Rework  worksheet, add-
ing  the  space  of  the  adjoining
unconfined  space. The  combined  spaces
must  have  enough  fresh air to supply  all
appliances  in  both  spaces.
VENTILATION  AIR
Ventilation  Air  From  Inside Building
This  fresh  air  would  come  from  an  adjoining
unconfined  space.  When  ventilating   to  an
adjoining  unconfined space, you  must
provide  two permanent openings: one  within
12
"
  of  the  ceiling and  one  within  12
"
  of   the
floor  on  the wall  connecting  the  two  spaces
(see options 1 and 2,  Figure  2). You  can  also
remove  door  into  adjoining  room (see option
3, Figure 2). Follow  the  National Fuel  Gas
Code  NFPA 54/ANS Z223.1. Section  5.3,  Air
for  Combustion  and Ventilation
  for  required
size of  ventilation grills or ducts
If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.
 Example:
 Gas  water  heater          40,000        Btu/Hr
 Vent  free  heater    +      20,000        Btu/Hr
 Total                         =     60,000        Btu/Hr
3. Add the Btu/Hr of all fuel burning appliances in the space.
     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                         Btu/Hr
     Gas furnace                                                                    Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas Fireplace logs                                                        Btu/Hr
     Other gas appliances* +                                              Btu/Hr
    Total                                =                                        Btu/Hr
    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                          Btu/Hr (maximum the space can support)
                         Btu/Hr (actual amount of Btu/Hr used)
         Example :  51,200 Btu/Hr(maximum the space can support)
                           60,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. See  Ventilation  Air  From
inside  Building
, page 5.
B.  Vent  room  directly  to  the  outdoors. See  Ventilation  Air  From  Outdoors, page 6 .
C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.
Figure  2 -Ventilation  Air  from  Inside  Building