GAS LINE INSTALLATION
Continued
VENTING INSTALLATION
CHIMNEY PIPE INSTALLATION
The  DESA  chimney  system  is  a  snap-lock,  double  wall  pipe.  It
consists of a stainless steel inner flue pipe(s), a galvanized outer
pipe, and a wire spacer.
Each section of pipe comes in lengths of 12, 18, 36, and 48 inches,
but the actual lineal gain for each is measured after each section is
fully connected. Lineal gain is the actual measurable length of a part
after two or more parts are connected.
MODEL NO.
DESCRIPTION
GAIN
V3612ST
See-Through"
52
3
/
4
"
Fireplace
48-12DM/48-12TM
Flue Pipe
46
5
/
8
"
36-12DM/48-12TM
Flue Pipe
34
5
/
8
"
STL-12D
Chase Style
1" to 12"
Termination
RTL-12D
Round Top Termination
7"
PIPE INSTALLATION
Place pipe assembly (inner and outer with wire spacer) over starter
collar. Inner pipe(s) fit inside inner pipe(s). Outer pipe fits outside
outer pipe.
Begin by aligning hemmed end of inner flue pipe into the inner starting
flue pipe of fireplace. Push down until hem “snap-locks” with lances. The
outer pipe is just the opposite, the female end has the lances. Continue the
same procedure for the outer pipe (see Figure 16). It is important to assure
the joints between the chimney sections are fully locked. Check by pulling
chimney upward after locking pipe hem(s). The chimney should not
come apart if properly locked. It is not necessary to add screws to keep
vertical or angled chimney runs together.
Figure 16 - Pipe Connection
 WARNING: The opening around the starter collar on
top of the fireplace must never be obstructed. Never use
blown insulation to fill the chimney enclosure.
FIRESTOP SPACERS
Firestop  spacers  are  required  at  each  point  where  the  chimney
penetrates a floor or ceiling joist space. Their purpose is twofold.
They  establish  and  maintain  the  required  clearance  between  the
outer pipe and combustible materials, they also serve as a shield
between floors as required by most codes.
When penetrating a floor or ceiling at an angle, use firestop spacer
number  30  FS-10D  (see 
Replacement  and  Accessory  Parts,
back page).
When the pipe passes through a framed opening into a living space
above, a firestop must be placed on the ceiling below (see Figure 17,
page 9). When the pipe passes through a framed opening into an attic
space above, a firestop must be placed on the attic floor above (see
Figure 18, page 9).
 CAUTION: When using a decorative appliance,
the damper must be removed or permanently locked
in the open position.
 WARNING: After ensuring that the gas valve is ON,
test  all  gas  piping  and  connections  for  leaks  after
installing or servicing. Correct all leaks at once.
  WARNING: Never use an open flame to check for
a leak. Apply a noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak. Correct all
leaks at once.
GASLINE INSTALLATION
CHIMNEY PIPE INSTALLATION
PIPE INSTALLATION
 
FIREST OP SPACERS
15" (381mm)
Galvanized
Outer Pipe
12 3/8" (314mm)
Stainless Inner
Pipe Lanced
Side Up
Hemmed
Ends
Note: An appropriate DESA hood (see Replacement and Accessory
Parts, page 16) must be installed when using an unvented gas log set.
24-12DM/48-12TM
Flue Pipe
22
5
/
8
"
18-12DM/48-12TM
Flue Pipe
16
5
/
8
"
12-12DM/48-12TM
Flue Pipe
10
5
/
8
"