FireplaceXtrordinair 44 DV XXL EF User Manual

Page of 56
1 6
Installation 
(for qualified installers only)
Travis Industries
4050114
1 0 0 - 0 1 1 4 9
Approved Vent Configurations
Restrictor Position
A vent restrictor is built into the appliance to adjust the flow rate of exhaust gases.  This ensures proper
combustion for all vent configurations.  Depending upon the vent configuration, you may be required to adjust
the restrictor position.  The charts for acceptable vent configurations detail the correct vent restrictor position.
With the face removed and 
the fireplace cool, reach 
above the firebox.
To Adjust the Restrictor:
To Access the Restrictor:
1
2
Determine the correct restrictor position (see the charts under 
"Approved Vent Configurations" - the factory position is #1).
Lift up the adjustment plate and move it so the correct notch 
falls into the slot on the adjustment bracket.
This restrictor is in position 1 
(factory setting).
This restrictor is in 
position 6.
Adjustment 
Bracket
To adjust, lift up on the 
adjustment plate and push it 
back.
WARNING: Use a glove to protect 
your hand from burns.
Adjustment 
Plate
# 7
# 2
etc.
Elbows
See the vent
configurations for
details on how
many elbows may
be used and in
what manner.
Measuring Vent
Lengths
6-1/4"
NOTE:
All measurements 
are for 8" diameter 
vent.
Vent 
Horizontal 
Run
Vent 
Height
43-1/8"
10-3/4" wide with 
1-3/4" to 
3-3/8" of overlap
Starter 
Section
12-3/8"
3-1/2"
Side 
View
1-3/4"
Vent Length
(2', 3', etc.)
NOTE:
Vent sections overlap 
each other by 1-3/4"
3-1/2"
8"