FireBox inSTALLATion
Figure 2 - Common Location of Fireplace
MINIMUM CLEARANCE TO 
COMBUSTIBLES
Back and sides of firebox 
1" min.
Adjacent wall 
12" min.
Chimney outer pipe surfaces  2" min.
Bottom of firebox to floor 
0" min. 
  WARNING:  Do  not  block 
required  air  spaces  with  insu-
lation  or  any  other  material. 
Do not obstruct effective open-
ing* of firebox with any type of 
facing  material.  Combustible 
material must not be in contact 
with black front face of firebox.  
*
(The  effective  opening  is  considered 
the  opening  where  actual  heat  output 
may occur.)
MANTEL CLEARANCES
Woodwork  such  as  wood  trims,  mantels  or 
any other combustible material projecting from 
the front face must not be placed within 9" of 
firebox effective opening. 
Combustible materials above and projecting 
more than 1 
1
/
2
" from the firebox front face 
(see Figure 4, page 5) must not be placed less 
than 12" from effective opening of the firebox 
(NFPA STD 211, Sec. 7-3.3.3).
Mantels  or  any  other  combustible  material 
may  also  come  up  to  the  side  edge  of  the 
black  metal  face  of  the  firebox  only  if  the 
projection from the front face falls within limits 
shown in Figure 5, page 5.
Spacers on Sides of 
Fireplace Provide 
Required 1" (2.5cm) 
Clearance
2" (5cm) Min. Clearance
From Pipe to 
Combustibles
3" (7.6cm)
12" (30.4cm) Min. From Perpendicular 
Side Wall to Fireplace Opening (Typ.)
Figure 3 - Firebox Clearances
Existing Wall
Projected Wall
12" (30.4 cm) to 
Perpendicular Wall
SELECTING LOCATION
To  determine  the  safest  and  most  efficient 
location  for  the  firebox,  you  must  take  into 
consideration the following guidelines:
1.  The location must allow for proper clear-
ances.
2.  Consider a location where the heat output 
will not be affected by drafts, air condition-
ing ducts, windows or doors.
3.  A  location  that  avoids  the  cutting  of 
joists or roof rafters will make installation 
easier.
4.  If an outside air kit is to be installed, ac-
cessibility to outside combustion air must 
be considered. This can also be achieved 
through  a  vented  crawl  space  in  some 
cases  (see  Optional  Outside Air  Kit  on 
page 6).
5.  Do not connect this firebox to a chimney 
system other than a DESA Heating, LLC 
chimney system.
6.  Install in an area providing ventilation and 
adequate combustion air.
7.  Due to high temperatures, do not locate 
this firebox in high traffic areas or near 
furniture or draperies.
8.  Provide  adequate  clearances  around 
air  openings  into  combustion  chamber. 
NEVER obstruct front opening of firebox 
or flow of combustion and ventilation air.
9.  Do not locate in or near an area where 
gasoline or other flammable liquids may 
be stored. The firebox area must be kept 
clear  and  free  from  these  combustible 
materials.
The typical installation for this fireplace is a 
projected installation which allows you to ex-
tend the fireplace any distance into the room. 
A projection may be ideal for a new addition 
on an existing, finished wall.