Desa (V)T32EN SERIES User Manual

Page of 40
www.desatech.com
111987-01D
8
VENTING INSTALLATION 
INSTRUCTIONS
NOTICE:  Read  these  instruc-
tions  completely  before  at-
tempting installation.
These models are tested and approved for use 
with DESA (direct-vent) pipe components and 
terminations.
The venting system must terminate on the outside of 
the structure and can not be attached to a chimney 
or flue system serving a separate solid fuel or gas 
burning appliance. A direct-vent appliance must 
have its own venting system. DO NOT common 
vent this appliance.
These models are approved to be vented either 
horizontally through an outside wall or vertically 
through a roof or chase enclosure using the fol-
lowing guidelines:
•  When venting system terminates horizontally 
on an outside wall, you may install a standoff 
if the termination cap is to be installed directly 
on a combustible finish such as vinyl, wood, 
stucco, etc.
•  Never  run  the  vent  downward  as  this  may 
cause  excessive  temperatures  which  could 
cause a fire.
•  Vent pipe air space clearances to combustibles 
are 1" on all sides except on the horizontal 
sections, which requires  2"  clearance  from 
the top of the pipe. Where the termination cap 
penetrates a combustible wall, 1" air space 
clearance is required.
•  Snorkel  terminations  are  required  when 
minimum clearance to grade cannot be met (see 
Figure 16 on page 12).
•  Have fireplace and selected vent components on 
hand to help determine the exact measurements 
when elbowing or offsetting. Always use wall 
firestops when penetrating walls and firestops 
when penetrating ceilings or attic spaces.
•  If using a venting configuration of only hori-
zontal venting with no vertical run, a 1/4" rise 
for every 12" of run toward the termination is 
required.
•  For installation of fireplace at elevations of 4000 
feet or greater, pay special attention to venting 
requirement recommendations.
 WARNING: Read all instruc-
tions completely and thoroughly 
before  attempting  installation. 
Failure to do so could result in 
serious injury, property damage 
or loss of life. 
NOTICE: Failure to follow these in-
structions will void the warranty. 
NOTICE: Do not seal termination 
cap to vent pipe. Cap must be 
removable  for  vent  inspection 
and maintenance.
INSTALLATION pRECAUTIONS
•  Wear gloves and safety glasses for protection
•  Use extreme caution when using ladders or 
when on roof tops
•  Be aware of electrical wiring locations in walls 
and ceilings
The following actions will void the warranty on 
your venting system:
•  Installation of any damaged venting component
•  Unauthorized modification of the venting sys-
tem (Do not cut or alter vent components)
•  Installation of any component part not manu-
factured or approved by DESA
•  Installation other than as instructed by these 
instructions
 WARNING: This gas fireplace 
and vent assembly must be vented 
directly to the outside. The venting 
system must NEVER be attached 
to a chimney serving a separate 
solid fuel burning appliance. Each 
direct-vent  gas  appliance  must 
use a separate vent system. Do not 
use common vent systems.
  WARNING:  Vent  pipe  air 
space clearances to combustibles 
are 1" on all sides except on the 
horizontal sections, which require 
2" clearances from the top of the 
pipe. Where the termination cap 
penetrates a combustible wall, 1" 
air space clearance is required.