Desa VTP22R User Manual

Page of 48
www.desatech.com
113261-01C
6
1.  Determine the volume of the space (length x 
width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: 
Space  size  20  ft.  (length)  x  16  ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)
 
If  additional  ventilation  to  adjoining  room  is 
supplied with grills or openings, add the volume 
of these rooms to the total volume of the space. 
2.  Multiply the space volume by 20 to determine the 
maximum Btu/Hr (kw) the space can support.
 
 __________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example:
 2560 cu. ft. (volume of space) x 20 = 
51,200 (maximum Btu/Hr the space can support)
3.  Add the Btu/Hr (kw) of all fuel burning appli-
ances in the space.
 
Vent-free heater 
 ________ Btu/Hr (kw)
 
Gas water heater* 
 ________ Btu/Hr (kw)
 
Gas furnace 
 ________ Btu/Hr (kw)
 
Vented gas heater 
 ________ Btu/Hr (kw)
 
Gas fireplace logs 
 ________ Btu/Hr (kw)
 
Other gas appliances* + ________ Btu/Hr (kw)
 
Total                            = ________ Btu/Hr (kw)
 
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors 
and vents to the outdoors.
 
Example: 
 
Gas water heater    ___________ Btu/Hr (kw)
 
Vent-free heater    ___________ Btu/Hr (kw)
 
Total  
  ___________ Btu/Hr (kw)
4.  Compare the maximum Btu/Hr (kw) the space can 
support with the actual amount of Btu/Hr (kw) used.
___________Btu/Hr (kw) (maximum the space can support)
___________Btu/Hr (kw) (actual amount of Btu/Hr used)
 
Example:
  51,200 Btu/Hr (15 kw) (maximum 
the space can support) 
 
 
62,000  Btu/Hr  (18.2  kw)  (actual 
amount of Btu/Hr used)
The space in the above example is a confined space 
because the actual Btu/Hr (kw) used is more than the 
maximum Btu/Hr (kw) the space can support. You must 
provide additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined 
space, remove door to adjoining room or add 
ventilation grills between rooms. See Ventilation 
Air From Inside Building.
B.  Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
AIR FOR COMBUSTION 
AND VENTILATION
Continued
C.  Install a lower Btu/Hr (kw) heater, if lower Btu/Hr 
(kw) size makes room unconfined. 
If the actual Btu/Hr (kw) used is less than the maxi-
mum Btu/Hr (kw) the space can support, the space 
is an unconfined space. You will need no additional 
fresh air ventilation.
 WARNING: If the area in which 
the  heater  may  be  operated  is 
smaller  than  that  defined  as 
an  unconfined  space  or  if  the 
building  is  of  unusually  tight 
construction, provide adequate 
combustion and ventilation air 
by one of the methods described 
in the National Fuel Gas Code, 
ANSI Z223.1/NFPA 54 Section 5.3 
or applicable local codes. 
VENTILATION AIR
Ventilation Air From Inside Building 
This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining 
unconfined space, you must provide two perma-
nent openings: one within 12" (30.5 cm) of the 
ceiling and one within 12" (30.5 cm) of the floor 
on the wall connecting the two spaces (see options 
1 and 2, Figure 2). You can also remove door into 
adjoining room (see option 3, Figure 2). Follow the 
National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
Section 5.3, Air for Combustion and Ventilation for 
required size of ventilation grills or ducts.
  40,000 (11.7)
  + 22,000   (6.4)
  = 62,000 (18.2)
Figure 2 - Ventilation Air from Inside 
Building
Or 
Remove 
Door into 
Adjoining 
Room, 
Option 3
Ventilation Grills 
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room, 
Option 1
12" (30,48 cm)
12" (30,48 cm)